LED
Colour
Function
H102
Yellow
FUE_FAU_1
H103
Yellow
FUE_FAU_2
H104
Yellow
FUE_AL_1
H105
Yellow
FUE_AL_2
H106
Yellow
HORN_1
LED
Colour
Function
H108
Yellow
IO_FAULT
H109
Yellow
IO_DIR
H110
Yellow
IO_1
H111
Yellow
IO_2
H112
Yellow
IO_3
H113
Yellow
IO_4
H114
Yellow
IO_5
H115
Yellow
IO_6
H100
Yellow
IO_7
H101
Yellow
IO_8
Building Technologies
Fire Safety & Security Products
Indication of outputs
Indications of programmable inputs / outputs
Condition
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Periphery board (2 loops) FCI2002-A1
Condition
Meaning
Off
Relay activated (default)
On
Relay not activated
Off
Active (default)
Slow
Open line
Fast
Short-circuit
On
Passive
Off
Relay not activated (default)
On
Relay activated
Off
Passive (default)
Slow
Open line
Fast
Short-circuit
On
Active
Off
Passive (default)
Slow
Open line
Fast
Short-circuit
On
Active
STATUS
Normal operation
I/O error (excess temperature, excess voltage, etc.)
I/O STATUS (push button S100)
I/O DIRECTION (push button S100)
High input (default)
Low input
High input (default)
Low input
High input (default)
Low input
High input (default)
Low input
High input (default)
Low input
High input (default)
Low input
High input (default)
Low input
High input (default)
Low input
DIRECTION
INPUT (default)
OUTPUT
INPUT (default)
OUTPUT
INPUT (default)
OUTPUT
INPUT (default)
OUTPUT
INPUT (default)
OUTPUT
INPUT (default)
OUTPUT
INPUT (default)
OUTPUT
INPUT (default)
OUTPUT