7-2. Operation Data

<Cooling>
Temperature
condition (°C)
Model name
RAS-
Indoor
Outdoor
B10GKVP-E
27/19
35/–
B13GKVP-E
B16GKVP-E
<Heating>
Temperature
condition (°C)
Model name
RAS-
Indoor
Outdoor
B10GKVP-E
20/–
7/6
B13GKVP-E
B16GKVP-E
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 7.5 m
Heat exchanger
Standard
pipe temp.
pressure
P (MPa)
T1 (°C)
0.9 to 1.1
13 to 15
0.8 to 1.0
11 to 14
0.7 to 0.9
8 to 11
Heat exchanger
Standard
pipe temp.
pressure
P (MPa)
T1 (°C)
2.2 to 2.4
37 to 39
2.5 to 2.7
42 to 45
2.8 to 3.0
48 to 49
– 21 –
Indoor
fan mode
T2 (°C)
42 to 44
High
42 to 45
High
43 to 47
High
Indoor
fan mode
T2 (°C)
0 to 3
High
0 to 2
High
0 to 2
High
Compressor
Outdoor
revolution
fan mode
(rps)
High
37
High
59
High
82
Compressor
Outdoor
revolution
fan mode
(rps)
High
54
High
65
High
86