Toshiba RAS-10GAVP-E Service Manual page 20

Toshiba air condition service manual
Hide thumbs Also See for RAS-10GAVP-E:
Table of Contents

Advertisement

RAS-B13GKVP-E/RAS-13GAVP-E, RAS-B16GKVP-E/RAS-16GAVP-E
P
Pressure measurement
Gauge attaching port
Vacuum pump connecting port
Deoxidized copper pipe
Outer dia. : 9.52mm(13),
12.7mm(16)
Thickness : 0.8mm
4-way valve
(STF-0108Z)
TS
Temp. measurement
NOTE :
• The maximum pipe length of this air conditioner is 25 m. When the pipe length exceeds 15m, the additional
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 200g)
INDOOR UNIT
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe
Outer dia. : 6.35mm
Thickness : 0.8mm
Sectional shape
of heat insulator
Muffler
Muffler
TD
Compressor
DA111A1F-20F1
Outdoor heat
exchanger
T2
Propeller fan
OUTDOOR UNIT
– 20 –
Temp. measurement
T1
TC
TA
Strainer
TO
Split capillary
Ø1.2 x 80
Ø1.2 x 80
TE
NOTE :
Max.
Min.
Chargeless : 15m
Charge : 20g/m
(16 to 25m)
Pulse motor
valve at liquid side
(CAM-B22YGTF-3)
Refrigerant amount : 0.96kg
Gas leak check position
Refrigerant flow (Cooling)
Refrigerant flow (Heating)
: 25m
: 2m