Lennox G32V Series Service Literature page 89

Hide thumbs Also See for G32V Series:
Table of Contents

Advertisement

PROBLEM 5: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER
Condition
5.1
− Unit operates with a cooling and
continuous fan demand.
− Combustion air blower energizes
Combustion air blower energizes
with Heating demand.
− Ignitor is energized but unit fails to
light.
LED#1−Alternating Slow Flash
LED#2−Alternating Slow Flash
PROBLEM 6: BURNERS LIGHT WITH A HEATING DEMAND BUT UNIT SHUTS DOWN
Condition
6.1
− Burners fire with a heating demand.
− Burners light but unit shuts off prior
− Burners light but unit shuts off prior
to satisfying T−stat demand.
− Diagnostic lights flash the pressure
switch code.
LED#1−Off
LED#2−Slow Flash
6.2
− Combustion air blower energizes with
a heating demand.
− Burners light but fail to stay lit.
B
li ht b t f il t
− After 5 tries the control diagnostics
flash the watchguard burners failed to
ignite code.
ignite code.
LED#1−Alternating Slow Flash
LED#2−Alternating Slow Flash
ENERGIZES, IGNITOR IS ENERGIZED. (CONT.)
Possible Cause
Check that gas is being supplied to
Miswiring of gas valve or loose con-
nections at multi−pin control amp
Malfunctioning gas valve or ignition
PREMATURELY
Possible Cause
Wrong concentric vent kit used for ter-
minating the unit.
Condensate drain line is not draining
Low pressure differential at the pres-
Sensor or sense wire is improperly
t
lit
Sensor or sense wire is broken.
Sensor or sensor wire is grounded to
Control does not sense flame.
5.1.1
the unit.
5.1.2
plugs or valve.
5.1.3
control.
6.1.1
6.1.2
properly.
6.1.3
sure switch.
6.2.1
installed.
6.2.2
6.2.3
the unit.
6.2.4
Page 89
Corrective Action/Comments
ACTION 1 − Check line pressure at the gas valve.
Pressure should not exceed 13" WC for both nat-
ural and propane. Line pressure should read a
minimum 4.5" WC for natural and 8.0"WC for pro-
pane.
ACTION 1 − Check for correct wiring and loose
connections. Correct wiring and/or replace any
loose connections.
ACTION 1 − Check that 24V is supplied to the gas
valve approximately 35 seconds after heat de-
mand is initiated.
ACTION 2 − Replace the valve if 24V is supplied
but valve does not open (check for excessive gas
line pressure before replacing gas valve).
ACTION 3 − Replace the control board if 24V is
not supplied to valve.
Corrective Action/Comments
ACTION 1 − Check vent termination kit installed.
1−1/2" dia. concentric vent (kit60G77) for 50 and
75 inputs and 2" dia. concentric vent (kit 33K97)
for 100 &125 inputs.
ACTION 1 − Check condensate line for proper
vent slope, and any blockage. Condensate
should flow freely during operation of furnace.
Repair or replace any improperly installed con-
densate lines.
ACTION 1 − Check for restricted vent inlet or ex-
haust. Remove all blockage.
ACTION 2: Check for proper vent sizing. See
installation instructions.
ACTION 1 − Check that sensor is properly lo-
cated (page 10) and that the sense wire is
properly attached to both the sensor and the
control.
ACTION 1 − Check for a broken sensor.
ACTION 2 − Test continuity across the sense
wire. If wire or sensor are damaged replace the
component.
ACTION 1 − Check for resistance between the
sensor rod and the unit ground.
ACTION 2 − Check for resistance between the
sensor wire and the unit ground.
ACTION 3 − Correct any shorts found in circuit.
ACTION 1 − Check the microamp signal from
the burner flame. If the microamp signal is be-
low 0.70 microamps, check the sense rod for
proper location or contamination.
ACTION 2 − Replace, clean, or relocate flame
sense rod. If rod is to be cleaned, use steel
wool or replace sensor. DO NOT CLEAN ROD
WITH SAND PAPER. SAND PAPER WILL
CONTRIBUTE TO THE CONTAMINATION
PROBLEM. NOTE: Do not attempt to bend
sense rod.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents