Electronic Ignition (See Ignition Sequence Below)
On a call for heat the SureLight control monitors the com-
bustion air blower pressure switch. The control will not be-
gin the heating cycle if the pressure switch is closed (by−
passed). Once the pressure switch is determined to be
open, the combustion air blower is energized. When the dif-
ferential in the pressure switch is great enough, the pres-
sure switch closes and a 15−second pre−purge begins. If the
pressure switch is not proven within 2−1/2 minutes, the con-
trol goes into Watchguard−Pressure Switch mode for a
5−minute re−set period.
After the 15−second pre−purge period, the SureLight ignitor
warms up for 20 seconds after which the gas valve opens
for a 4−second trial for ignition. G32V units with board
24L85, 56L83 or 63K89: the ignitor energizes for the first
second of the 4−second trial. Units equipped with board
97L48: ignitor energizes during the trial until flame is
sensed. If ignition is not proved during the 4−second period,
the control will try four more times with an inter purge and
warm−up time between trials of 35 seconds. After a total of
five trials for ignition (including the initial trial), the control
goes into Watchguard−Flame Failure mode. After a 60−min-
ute reset period, the control will begin the ignition sequence
again.
The SureLight control board has an added feature that pro-
longs the life of the ignitor. After a successful ignition, the
SureLight control utilizes less power to energize the ignitor
on successive calls for heat. The control continues to ramp
down the voltage to the ignitor until it finds the lowest
amount of power that will provide a successful ignition. This
amount of power is used for 255 cycles. On the 256th call
for heat, the control will again ramp down until the lowest
power is determined and the cycle begins again.
1
É É
ON
É É
OFF
É É É É É É É É É É É É É É É É É É É É É É É É É
DEMAND
É É É É É É É É É É É É É É É É É É É É É É É É É
É É É É É É É É É É É É É É É É É É É É É É É É É É É
CAB
IGNITOR
GAS VALVE
INDOOR BLOWER
1
É
É É
ON
OFF
É É É É É É É É É É É É É É É É É É É É É É É É É
DEMAND
É É É É É É É É É É É É É É É É É É É É É É É É É É É
É É É É É É É É É É É É É É É É É É É É É É É É É
CAB
IGNITOR
É É É É É É É É É É É É É É É É É É É É É É É É É É É
GAS VALVE
INDOOR BLOWER
*All controls: blower on time will be 45 seconds after gas valve is energized. Blower off time will depend on OFF TIME" Setting.
Ignition Sequence Board: 63K89, 24L85 and 56L8301
15
Pre −Purge
Ignitor Warmup
É É É É É É É É
É É É É É É É É
Ignition Sequence Board 97L4801
15
Pre −Purge
Ignitor Warmup
É É É É É É É É É É
5. Two−Stage Control (A86)
G32V−1 through −4 units
G32V−1 through −4 units are equipped with a two−stage
control (figure 10). The two−stage board acts as a go be-
tween from the indoor thermostat to the SureLight ignition
board. The board can be utilized in three modes: with a
SINGLE−STAGE thermostat, a TWO−STAGE thermostat or
with a second−stage (high fire) delay called W2 TIMED. The
two−stage board is equipped with a jumper (see figure 10)
which changes operating modes and a jumper which ad-
justs second−stage heat delay during W2 TIMED mode.
While in the single−stage thermostat mode (one−stage
jumper setting), the unit will always operate on second−
stage heat. The combustion air blower (B6) will operate on
high speed and indoor blower (B3) will operate on heating
speed. While in the two−stage thermostat mode the unit will
operate on first−stage heat (low fire). The combustion air
blower (B6) and indoor blower will operate on low speed.
The unit will switch to second−stage heat (high fire) on call
from the indoor thermostat W2. While in the W2 TIMED
mode (factory setting 8 minutes) the unit will fire on first−
stage heat (low fire) with the combustion air blower (B6)
and indoor blower (B3) operating on low speed. After a set
time delay the unit switches to second−stage heat (high
fire). The combustion air blower and indoor blower also
switch to second−stage heat mode.
34
35
38
Trial for
Blower On"
Ignition
Delay
É É É É É É É É É É É É É É
É É É É É É É É É É É É É É
34
38
Trial for
Blower On"
Ignition
Delay
É É É É É É É É É É É É É É
É É É É É É É É É É É É É É
Page 13
80
5 SEC
Post
Purge
É É É É É É É É É
80
5 SEC
Post
Purge
É É É É É É É É É
É É É É É É É É É