10.2

IE/AS-i Link PN IO

Description
Figure 10-4
● Single or double AS-Interface master for connection of 62 or 124 AS-Interface slaves (for
dual master)
● Compact plastic housing with IP20 degree of protection for installation on a DIN rail
● Full graphics display and control buttons on the front of the housing for commissioning
the entire lower-level AS-i line and diagnostics on site
● Optional use of the C-PLUG memory medium (does not ship with the product) for storage
of device parameters to allow quick device exchange
Features
Connector - Industrial Ethernet
Connector - AS-i
Transmission rate - Industrial Ethernet
Power supply
Integrated 2-port real-time switch
Diagnostic LEDs
C-PLUG slot
● Suitable / available or according to the specified standard.
Functions
● AS-Interface bus cycle time 5 ms for 31 slaves, 10 ms for 62 slaves
● Use as single and double AS-interface master for the connection of 62 AS-interface
slaves and integrated analog value monitoring
● Integrated Web server through which configuration with Web-based Management is also
possible
Industrial Ethernet
System Manual, 09/2019, C79000-G8976-C242-10
IE/AS-i LINK PN IO
10.2 IE/AS-i Link PN IO
IE/AS-i Link PN IO
2x RJ45 (switched)
Screw connector
10/100 Mbps
24 VDC or via AS-i
Gateways