Communications processors for SIMATIC S7
8.2 Communications processors for SIMATIC S7-300
Article numbers
Device
CP 343-1 Lean
SIPLUS CP 343-1 Lean
CP 343-1
SIPLUS CP 343-1
CP 343-1 Advanced
SIPLUS CP 343-1 Ad-
vanced
CP 343-1 ERPC
(Enterprise Connect)
316
Description
To connect SIMATIC S7-300 in Industrial Ethernet using TCP/IP and
UDP multicast. S7 communication, open communication
(SEND/RECEIVE), FETCH/WRITE, PROFINET IO device, MRP,
integrated 2-port switch ERTEC
For an extended temperature range and harsh environmental loads.
To connect SIMATIC S7-300 in Industrial Ethernet using TCP/IP and
UDP, multicast. S7 communication, open communication
(SEND/RECEIVE), FETCH/WRITE, PROFINET IO device, MRP,
integrated 2-port switch ERTEC
Ambient temperature from 0 °C to +60 °C
Ambient temperature from -25 °C to +60 °C
For connecting SIMATIC S7-300 in Industrial Ethernet via ISO and
TCP/IP; PROFINET IO controller or PROFINET IO device, MRP,
integrated 2-port switch ERTEC. S7 communication, open communi-
cation (SEND/ RECEIVE), FETCH/WRITE, with and without
RFC 1006
For an extended temperature range and harsh environmental loads.
For connecting SIMATIC S7-300 in Industrial Ethernet using ISO and
TCP/IP, PROFINET IO controller or PROFINET IO device. S7 com-
munication, open communication (SEND/ RECEIVE),
FETCH/WRITE, with and without RFC 1006
Ambient temperature from 0 °C to +60 °C
Ambient temperature from -25 °C to +70 °C
For connection to SIMATIC S7-300 in Industrial Ethernet;
1x 10/100/1000 Mbps; 2 x 10/100 Mbps (IE SWITCH); RJ45 ports;
TCP; UDP; ISO; PROFINET IO controller and IO device, S7 commu-
nication (Client and Server);
Open communication (SEND/ RECEIVE)
Without security function
With security function, firewall, VPN and PROFIenergy (controller and
device)
For connection to SIMATIC S7-300 in Industrial Ethernet;
1x 10/100/1000 Mbps; 2 x 10/100 Mbps (IE SWITCH); RJ45 ports;
TCP; UDP; ISO; PROFINET IO controller and IO device, S7 commu-
nication (Client and Server);
Open communication (SEND/ RECEIVE)
Ambient temperature from 0 °C to +60 °C
For connecting SIMATIC S7-300 in Industrial Ethernet and to support
the database connection of the SIMATIC S7-300 to various data-
bases, TCP/UDP. S7 communication, open communication (SEND/
RECEIVE), with and without RFC 1006
Article number
6GK7343-1CX10-0XE0
6AG1343-1CX10-4XE0
6AG1343-1CX10-2XE0
6GK7343-1EX30-0XE0
6AG1343-1EX30-4XE0
6AG1343-1EX30-7XE0
6GK7343-1GX30-0XE0
6GK7343-1GX31-0XE0
6AG1343-1GX30-4XE0
6GK7343-1FX00-0XE0
System Manual, 09/2019, C79000-G8976-C242-10