SCALANCE network components
4.5 SCALANCE X Industrial Ethernet Switches
4.5.12.3

Interfaces

Device
Total number of
available ports
X204RNA
X204RNA EEC
Of which 2 are combo ports
1)
Note
TP connectors of SCALANCE X204RNA EEC
2x RJ45 for connecting two end devices / network structures without PRP-1 capability and
optionally 2x RJ45 or 2x SFP modules for connecting network structures capable of PRP. If
an SFP module is inserted, the corresponding RJ45 jack is deactivated.
Example: If SFP module "PRP A" is inserted, the TP Interface "PRP A" has no function.
Note
SCALANCE X200RNA
The networks LAN A and/or LAN B can have PROFINET or IRT functionality. These cannot,
however, be transferred via the SCALANCE X200RNA because PRP does not support this.
PRP functionality is not impaired by using PROFINET or IRT components in the LAN A and
LAN B networks.
4.5.12.4

Article numbers

Device
SCALANCE X204RNA (PRP)
SCALANCE X204RNA (HSR)
SCALANCE X204RNA EEC (PRP)
SCALANCE X204RNA EEC (HSR)
SCALANCE X204RNA EEC
(PRP/HSR)
156
Twisted pair
10/100 Mbps
4
4x RJ45
(of which 2x PRP
ports)
4
Max. 4x RJ45
1)
(of which 2x PRP
ports)
Description
4x 100 Mbps RJ45 ports
2x 100 Mbps RJ45 ports and
2x 100 Mbps combo ports
Fiber-optic cables
10/100 Mbps
100/1000 Mbps
-
-
Supported modes
PRP ↔ standard Ethernet
PRP ↔ HSR link
HSR ↔ Standard Ethernet;
HSR ↔ PRP coupling
PRP ↔ standard Ethernet
HSR ↔ Standard Ethernet;
HSR ↔ PRP coupling
PRP ↔ Standard Ethernet;
HSR ↔ Standard Ethernet;
HSR ↔ PRP link
System Manual, 09/2019, C79000-G8976-C242-10
Combo ports
-
-
-
2x SFP (100 Mbps)
as PRP ports
Article number
6GK5204-0BA00-2KB2
6GK5204-0BA00-2MB2
6GK5204-0BS00-3LA3
6GK5204-0BS00-2NA3
6GK5204-0BS00-3PA3