Viessmann Vitodens 200-W Series Installation And Service Instructions Manual page 83

Wall mounted
Table of Contents

Advertisement

Fault codes
(cont.)
Displayed
Const.
fault code
EA
X
Eb
X
EC
X
Ed
X
EE
X
Weath.-
System characteris-
comp.
tics
X
Burner in a fault state Ionisation current
X
Burner in a fault state Repeated flame
X
Burner in a fault state Parameter fault
X
Burner in a fault state Internal fault
X
Burner in a fault state Flame signal is not
Cause
Measures
Check flue system; reme-
outside permissible
dy flue gas recirculation if
range during cali-
required.
bration (deviation
In open flue operation,
from previous level
prevent high incidence of
too great)
dust in the combustion air.
Press reset button R.
Following several unsuc-
cessful reset attempts, re-
place boiler coding card
and press reset button R.
Check gap between ioni-
loss during calibra-
sation electrode and burn-
tion
er gauze assembly (see
page 32).
Check allocation of gas
type (see page 26).
Check flue system; reme-
dy flue gas recirculation if
required.
Press reset button R.
Press reset button R
during calibration
or
Replace boiler coding
card and Press reset but-
ton R.
Replace control unit.
Check gas supply (gas
present or too
pressure and gas flow
weak at burner
switch).
start.
Check gas train.
Check ionisation elec-
trode and connecting ca-
ble.
Check ignition:
Connecting leads to ig-
nition module and igni-
tion electrode
Ignition electrode gap
and contamination (see
page 32).
Check condensate drain.
Press reset button R.
Troubleshooting