Viessmann Vitodens 200-W Series Installation And Service Instructions Manual page 53

Wall mounted
Table of Contents

Advertisement

Heating circuit 1, heating circuit 2, heating...
Coding in the delivered condition
Pump control in "Only DHW"
F6:25
In the "Only DHW" operating
mode, the circulation pump in the
heating circuit connection set is
constantly on (only for constant
temperature control units)
Pump control in "Standby mode"
F7:25
In "standby mode" the circulation
pump in the heating circuit connec-
tion set is constantly on (only for
constant temperature control units)
Start temperature raising
F8:-5
Temperature limit for terminating
reduced mode -5 °C, see example
on page 100.
Observe the setting of coding ad-
dress "A3". (only for weather-com-
pensated control units)
End temperature raising
F9:-14
Temperature limit for raising the re-
duced set room temperature
-14
C, see example on page 100.
º
(only for weather-compensated
control units)
Set flow temperature increase
FA:20
Raising the set boiler water tem-
perature or set flow temperature by
20 % when changing from opera-
tion with reduced room tempera-
ture to operation with standard
room temperature. See example
on page 100 (only for weather-
compensated control units).
Duration set flow temperature increase
Fb:60
Duration for raising the set boiler
water temperature or set flow tem-
perature (see coding address "FA")
60 min. See example on page 100
(only for weather-compensated
control units).
(cont.)
Possible change
F6:0
In the "Only DHW" operating mode,
the circulation pump in the heating
circuit connection set is constantly
off
F6:1
In the "Only DHW" operating mode,
to
the circulation pump in the heating
F6:24
circuit connection set is started 1 to
24 times per day for 10 min each
time.
F7:0
In "standby mode" the circulation
pump in the heating circuit connec-
tion set is constantly off
F7:1
In "Standby mode", the circulation
to
pump in the heating circuit connec-
F7:24
tion set is started 1 to 24 times per
day for 10 min each time.
F8:+10
Temperature limit adjustable from
to
+10 to -60 °C
F8:-60
F8:-61
Function disabled
F9:+10
Temperature limit for raising the set
to
room temperature to the value se-
F9:-60
lected for standard mode adjustable
from
+10 to -60 °C
FA:0
Temperature rise adjustable from 0
to
to 50 %
FA:50
Fb:0
Duration adjustable from 0 to
to
300 min;
Fb:300
Code 1
53