Connections on the heating water side

A
B
C
D
E
F
Fig. 4
Expansion vessel
A
Safety valve
B
Heating flow
C
D
Cylinder flow
Cylinder return
E
Heating return
F

Flue gas connection

Note
The labels "System certificate" and "Skoberne GmbH
flue system" enclosed with the technical documenta-
tion may only be used in conjunction with the
Viessmann flue system made by Skoberne.
Do not carry out commissioning until the following
conditions are met:
Free passage through the flue gas pipes.
Flue system with positive pressure is gas-tight.
Apertures for ensuring sufficient combustion air sup-
ply are open and cannot be closed off.
Applicable regulations on installing and commission-
ing flue systems have been followed.
Connect the boiler to the on-site pipework.
Note
Connection layout shown with the connection sets
available as accessories.
Provide the required connections when using on-site
fittings.
Connect the balanced flue.
Flue system installation instructions
Danger
Leaking or blocked flue systems or an insuffi-
cient supply of combustion air cause life threat-
ening poisoning due to carbon monoxide in the
flue gas.
Ensure the flue system functions correctly. Aper-
tures for combustion air supply must not be able
to be closed off.
Installation sequence