Coding - Viessmann Vitodens 200-W Series Installation And Service Instructions Manual

Wall mounted
Table of Contents

Advertisement

Code 1
Heating circuit 1, heating circuit 2, heating...

Coding

Coding in the delivered condition
Priority DHW heating
A2:2
Cylinder priority applicable to heat-
ing circuit pump and mixer
Economy function outside temperature
A5:5
With heating circuit pump logic
function (economy control): Heat-
ing circuit pump "OFF" if outside
temperature (OT) is 1 K higher
than the set room temperature
(RT
set
OT
>
er-compensated control units)
Parameter address A5:...
1
2
3
4
5
6
7
to
15
Coding in the delivered condition
Extended economy function adjusted outside temperature
A6:36
Extended economy control disa-
bled (only for weather-compensa-
ted control units)
50
)
RT
+ 1 K (only for weath-
set
With heating circuit pump logic function: Heating circuit pump "OFF"
OT
RT
+ 5 K
>
set
OT
RT
+ 4 K
>
set
OT
RT
+ 3 K
>
set
OT
RT
+ 2 K
>
set
OT
RT
+ 1 K
>
set
OT
RT
>
set
OT
RT
- 1 K
>
set
OT
RT
- 9 K
>
set
(cont.)
Possible change
A2:0
Without cylinder priority applicable to
heating circuit pump and mixer
A2:1
Cylinder priority only applicable to
mixer
A2:3
Reduced priority applicable to mixer
to
(the heating circuit receives a re-
A2:15
duced amount of energy)
A5:0
Without heating circuit pump logic
function
A5:1
With heating circuit pump logic func-
to
tion: Heating circuit pump "OFF";
A5:15
see following table
Possible change
A6:5
Extended economy control enabled;
to
i.e. the burner and heating circuit
A6:35
pump will stop and the mixer will be
closed at a variable value, adjusta-
ble between 5 and 35 °C plus 1 °C.
The base value is the adjusted out-
side temperature. This value is
based on the actual outside temper-
ature and a time constant, which
takes the cooling down of an aver-
age building into consideration.