Minimum heating water flow rate
The minimum heating water flow rate through the heat pump
must be assured in all operating states of the heating system.
This can be accomplished. for example, by installing a dual dif-
ferential pressureless manifold.
The frost protection function of the heat pump manager is active
whenever the heat pump manager and the heat circulating
pumps are ready for operation. The system must be drained if
the heat pump is taken out of service or in the event of a power
failure. If heat pump systems are implemented in buildings where
a power failure cannot be detected (holiday homes etc.), the
heating circuit should be operated with suitable frost protection.

7.3 Heat source connection

The following procedure must be observed when making the
connection:
Connect the well pipes to the heat pump's flow and return.
ATTENTION!
It is essential that the dirt trap included in the accessories pack is
installed in the return (inlet).
ATTENTION!
The well water must comply with the required water quality standards
(see see Cap. 9.4 on pag. 10).
The hydraulic integration diagram must be adhered to.
EN-6

7.4 Temperature sensor

The following temperature sensors are already installed or must
be installed additionally:
Outside temperature sensor (R1) supplied (NTC-2)
Return temperature heating circuit (R2) installed (NTC-10)
Return temperature primary circuit (R24) installed (NTC-10)
Flow temperature heating circuit (R9) installed (NTC-10)
Flow temperature primary circuit (R6) installed (NTC-10)
7.4.1 Sensor characteristic curves
Temperature in °C
NTC-2 in k
NTC-10 in k
15
20
2.9
2.4
14.9
12.1
The temperature sensors to be connected to the heat pump man-
ager must correspond to the sensor characteristic curve illus-
trated in Fig. 7.2. The only exception is the outside temperature
sensor included in the scope of supply of the heat pump (see Fig.
7.3)
70
60
50
40
30
20
10
0
-20
-15
Fig. 7.2: Sensor characteristic curve NTC-10
20
18
16
14
12
10
8
6
4
2
0
-20
-15
Fig. 7.3:Sensor characteristic curve NTC-2 according to DIN 44574 Out-
side temperature sensor
452234.66.57 · FD 9908
-20
-15
-10
14.6
11.4
8.9
67.7
53.4
42.3
25
30
35
40
2.0
1.7
1.4
1.1
10.0
8.4
7..0
5.9
-10
-5
0
5
10
15
20
25
External temperature in [°C]
-10
-5
0
5
10
15
20
25
External temperature in [°C]
WIH 120TU
-5
0
5
10
7.1
5.6
4.5
3.7
33.9
27.3
22.1
18.0
45
50
55
60
1.0
0.8
0.7
0.6
5.0
4.2
3.6
3.1
30
35
40
45
50
55
60
30
35
40
45
50
55
60