Johnson Controls TEC22 4-3 Series Installation Instructions Manual page 8

Lonworks networked multi-stage economizer thermostats
Table of Contents

Advertisement

Table 2: Installer Configuration Menu (Part 3 of 5)
Parameter
Description and Default
Appearing
on Display
TOccTime
Sets the duration of the Tempo-
rary Occupancy Time (when the
thermostat is in the Unoccupied
mode) when a Schedule Over-
ride Function is enabled using ei-
ther the Main User Menu or DI1
or DI2 configured as a temporary
override remote contact
(RemOVR).
Sets the effective duration of the
Temporary heating or cooling
setpoints set using the up/down
arrow keys.
default: 3.0 hrs
Cal RS
Sets the desired room air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C°C
Cal OS
Sets the desired outdoor air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C°
H stage
Reverts the operation of a two-stage
thermostat to a single-stage
thermostat when the second heating
stage is not needed.
Default: 2.0
C stage
Reverts the operation of a two-stage
thermostat to a single-stage
thermostat when the second cooling
stage is not needed.
Default: 2.0
H lock
Discontinues heating operation in
response to the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
Default: 120°F/49°C
C lock
Discontinues cooling operation in
response to the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected. C lock
does not disable economizer free
cooling operation.
Default: -40°F/-40°C
4
Sets the number of events within a
2/4event
24-hour period.
Default: 2.0
8
TEC22x4-3 L
W
ON
® Networked Multi-Stage Economizer Thermostats Installation Instructions
ORKS
Selection Options
Range: 0.0 to 12.0 hrs adjustable in 1-hour increments
Range: -5.0F°/-2.5C° to 5.0F°/2.5C° adjustable in 1.0F°/0.5C°
increments
Range: -5.0F°/-2.5C° to 5.0F°2.5C° adjustable in 1.0F°/0.5C°
increments
(1.0): One Stage
(2.0): Two Stages
(1.0): One Stage
(2.0): Two Stages
Range: -15°F/-26°C to 120°F/49°C adjustable in 5F°/5C° increments
Range: -40°F/-40°C to 95°F/35°C adjustable in 5F°/5C° increments
(2.0): Two events (one occupied and one unoccupied) within a
24-hour period
(4.0): Four events (two occupied and two unoccupied) within a
24-hour period