Note: For more details on wiring the
L
W
network, refer to the
ON
ORKS
L
W
Network Layout Technical Bulletin
ON
ORKS
(LIT-1162150).
2. Carefully push any excess wire back into the wall.
Seal the hole in the wall with fireproof material to
prevent drafts from affecting the ambient
temperature readings.
3. Reinsert the screw terminal blocks onto the PCB.
4. Reattach the L
W
ON
ORKS
the LON terminal block. See Figure 5.
Note: If inserting multiple wires into the terminals, be
sure to properly twist wires together prior to inserting
them in the terminal connectors.
5. Reattach the thermostat cover to the mounting
base (top side first).
6. Use a Phillips-head screwdriver to reinstall the
security screw on the bottom of the thermostat
cover.
Five-Pole
Left Top Connector
Y2
Y1
L
W
ON
ORKS
Bus Terminals
1
2
Eight-Pole Bottom Connector
EC
Aux
9
10
Figure 5: Terminal Blocks
Y2
Y1
G
RC
Cool 1
Cool 2
Fan
24 VAC
Thermostat Power
TEC22x4-3 L
W
® Networked Multi-Stage Economizer Thermostats Installation Instructions
ON
ORKS
communication wires to
Three-Pole
Right Top Connector
RH W1 W2
G
RC
C
6
3
4
5
7
8
OS
MS
DI1 DI2 RS
Scom
11 12
13
14
15
16
C
RH
W1
W2
Heat 1 Heat 2
If using the same power source
for the thermostat and heating loads,
install a jumper across RC and RH.
Figure 6: Wiring the TEC22x4-3 Thermostats
Table 1: Terminal Identification (See Figure 5.)
Number
Label
1
Y2
2
Y1
3
G
4
RC
5
C
6
RH
7
W1
8
W2
9
EC
10
Aux
11
DI1
12
DI2
13
RS
14
Scom
15
OS
16
MS
Blank
Blank
Isolated Contact
• Lighting
• On/Off Actuation
• Exhaust Fan
EC
Aux
DI1
DI2
RS
Aux
Remote
Room
Sensor
Function
Energizes on a call for second-stage
cooling.
Energizes on a call for first-stage
cooling.
Energizes fan in accordance with
selected fan mode.
24 VAC from equipment transformer
24 VAC (Common) from equipment
transformer
24 VAC for heating stage
Energizes on a call for first-stage
heating.
Energizes on a call for second-stage
heating.
0 to 10 VDC Economizer Actuator
Output
Auxiliary output
Configurable Digital Input 1
Configurable Digital Input 2
Remote Room Temperature Sensor
Sensor Common
Auxiliary/Outdoor Air Sensor
Mixed Air Temperature Sensor
L
W
Bus
ON
ORKS
L
Bus Terminal
Scom
MS
OS
Supervisory
Controller
Remote
Monitoring
Auxiliary/
Supply
Outdoor
Temperature
Air Sensor
Sensor
W
ON
ORKS
3