Srm1(-V2) Communications Functions; Host Link Communications - Omron CPM1 Programming Manual

Hide thumbs Also See for CPM1:
Table of Contents

Advertisement

PC Setup
Word
Bit
DM 6645
00 to 03
Port settings
00: Standard (1 start bit, 7-bit data, 2 stop bits, even parity, 9,600 bps)
01: Settings in DM 6646
(Other settings will cause a non-fatal error, the default setting (00) will be
used, and AR 1302 will turn ON.)
04 to07
CTS control settings
0: Disable
1: Set
08 to 11
Link area for 1:1 PC Link
0: LR 00 to LR 15
(Other settings: Disabled)
12 to 15
Communications mode
0: Host Link; 1: No-protocol; 2: 1:1 PC Link Slave;
3: 1:1 PC Link Master; 4: 1:1 NT Link
(Other settings will cause a non-fatal error, the Host Link setting will be
used, and AR 1302 will turn ON.)
Connecting the Cables
4-4

SRM1(-V2) Communications Functions

4-4-1 Host Link Communications

When creating a 1:1 PC Link with a CPM2A/CPM2C PC, use a Programming
Device to make the following settings to the PC Setup (DM 6645) in the Master
and Slave.
Function
For information on the 1:1 PC Link settings of another OMRON PC, refer to that
PC's Operation Manual.
This section describes the RS-232C connection.
The RS-232C cable used for 1:1 PC Links is a cross connection cable. When
there is no CTS control on the RS-232C port, the connection is made as shown
in the following diagram. With the CPM2C, the CPM2C-CN111 and CS1W-
CN118 connecting cables are used.
RS-232C port
Signal Pin No.
Host Link communications were developed by OMRON for the purpose of con-
necting PCs and one or more host computers by RS-232C cable, and controlling
PC communications from a host computer. Normally the host computer issues a
command to a PC, and the PC automatically sends back a response. Thus the
communications are carried out without the PCs being actively involved. The
PCs also have the ability to initiate data transmissions when direct involvement
is necessary.
In general, there are two means for implementing Host Link communications.
One is based on C-mode commands, and the other on FINS (CV-mode) com-
Section
Master
Setting
Any
0
0
3
RS-232C port
Signal Pin No.
Recommended cables
XW2Z-200T:
XW2Z-500T:
Hood
4-4
Slave
Setting
Any
0
0
2
2m
5m

Advertisement

Table of Contents
loading

This manual is also suitable for:

Srm-v2Cpm1aCpm2aSrm1Cpm2c