Algoworks Utility Programs Limits - Siemens Cerberus CS1140 Planning

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

7.4

AlgoWorks utility programs limits

7.4.1
Limit of SmartHandy (SWE11-A)
Fire & Security Products
Siemens Building Technologies Group
Limit of SmartHandy software
The current SmartHandy software has a limitation of 2400 nodes, i.e. the total of all ELE-
MENTS, ZONES, SECTIONS and AREAS must not exceed 2400.
Trying to open a station with more than 2400 nodes will produce the SmartHandy error
message 'Too many DB records' and the SmartHandy program will abort.
Limit of solid state disk
If there is not sufficient space on the internal disk of the WorkAbout to copy the station file
from AlgoWorks to the WorkAbout, AlgoWorks reports 'Disk
'Dxxxxx.DBF not transmitted'. Ü Delete no longer needed files using the Work-
About menu functions.
Trying to open a station when there is not enough space on the internal disk (to create the
temporary file which the SmartHandy program needs), the WorkAbout error message
'Error in HANDY\LOADDB: Disk full' is displayed. Ü Delete no longer needed
files using the WorkAbout menu functions.
full' and
23