Siemens SIMATIC S7-400 Hardware And Installation Manual page 31

Hide thumbs Also See for SIMATIC S7-400:
Table of Contents

Advertisement

Step 2: Mounting the Rack
Screw the rack to the base.
Is the base material a grounded metal plate or a grounded equipment plate?
If so: Establish a low-impedance connection between rack and base material.
With painted and anodized metals, for example, use a suitable contact agent or
special contact washers.
If not: No special measures are required.
Mounting Screws
You have a choice of the following types of screw for securing a rack:
M6 cylinder-head screw to
ISO 1207/ISO 1580 (DIN 84/DIN 85)
M6 hex. screw to ISO 4017 (DIN 4017)
Step 3: Connecting the Rack to the Chassis Ground
Connect the rack to the chassis ground. A threaded bolt is provided for this
purpose on the bottom left of the rack.
Minimum cross-section of the conductor to the chassis ground: 10 mm
If the S7-400 is mounted on a mobile rack, you must provide a flexible conductor to
the chassis ground.
Note
Always ensure that there is a low-impedance connection to the chassis ground
(see the figure below). You achieve this with the shortest possible, low-resistance
conductor with a large surface to establish large-area contact.
S7-400 and M7-400 Programmable Controllers, Installation Manual
C79000-G7076-C424-01
www.gkbpx.com
Screw Type
Installing the S7-400
Explanation
Choose the screw length according to your
assembly.
You also need "6.4" washers to ISO 7092
You also need "6 4" washers to ISO 7092
(DIN 433).