Networking
Lengths of Spur Lines
If you do not fit the bus cable directly at the bus connector (for example, when
using a PROFIBUS-DP bus terminal), you must take into account the maximum
possible spur line length.
The following table gives the maximum lengths of spur lines allowed per bus
segment:
Upward of 3 Mbps use PG connecting cable, order no. 6ES7 901-4BD00-0XA0, to
connect the programming device or PC. You can use two or more PG connecting
cables with this order number in one bus configuration. Different spur lines are not
allowed.
Table 5-3
Lengths of Spur Lines per Segment
Transmission Rate
9.6 to 93.75 Kbps
187.5 Kbps
500 Kbps
1.5 Mbps
3 to 12 Mbps
5-16
www.gkbpx.com
Max. Lengths of Spur
No. of Nodes per Spur Line Length
Lines per Segment
96 m
75 m
30 m
10 m
-
S7-400 and M7-400 Programmable Controllers, Installation Manual
of ...
1.5 m or 1.6 m
3 m
32
32
32
25
20
10
6
3
-
-
C79000-G7076-C424-01