Siemens SIMATIC S7-400 Hardware And Installation Manual page 160

Hide thumbs Also See for SIMATIC S7-400:
Table of Contents

Advertisement

Starting Up
Startup if preset config.
actual config. = yes (default)
CPU goes into RUN
To set the "Startup" parameter, see also the Reference Manual , Chapter 4, the
manual C onfiguring Hardware and Communication Connections with STEP 7 V5.0,
and the online help for STEP 7.
6-18
www.gkbpx.com
Startup if preset config.
The CPU remains at STOP and, after the time set in the
"module time limits" parameter, the BUSF LED flashes.
Flashing of the BUSF LED indicates that at least one
slave will not respond. In this case, check whether all
slaves are switched on or display the content of the
diagnostic buffer (see Configuring Hardware and
Communication Connections with STEP 7 V5.0 ).
S7-400 and M7-400 Programmable Controllers, Installation Manual
actual config. = no
C79000-G7076-C424-01