Siemens SIMATIC S7-400 Hardware And Installation Manual page 114

Hide thumbs Also See for SIMATIC S7-400:
Table of Contents

Advertisement

Networking
Number of Nodes
(default: 32)
1 PG port (reserved)
Observe the CPU-related maximum numbers in the Reference Manual , Chapter 4
*
MPI/PROFIBUS-DP Addresses
In order for all nodes to be able to communicate with one another, you must assign
them an address:
In the MPI network, an MPI address
A PROFIBUS-DP address in the PROFIBUS-DP network
Default MPI Addresses
The following table shows the default MPI address and the max. MPI address with
which the devices are shipped:
Node (Device)
Programming device
OP
CPU
Note
If you change the parameter assignment of the highest MPI address of the
MPI/DP interface, the new address remains set even after memory reset, voltage
failure or removing/inserting the CPU.
Rules for MPI Addresses
Observe the following rules before assigning MPI addresses:
All MPI addresses in an MPI network must be different.
The highest possible MPI address must be
and must be set to the same value for all nodes. (Exception: connecting a
programming device to two or more nodes.)
5-4
www.gkbpx.com
MPI
127
of which:
Default MPI Address
S7-400 and M7-400 Programmable Controllers, Installation Manual
PROFIBUS DP
127 *
1 master (reserved)
1 PG port (reserved)
125 slaves or other masters
Default Highest MPI
Address
0
1
2
the highest actual MPI address
C79000-G7076-C424-01
32
32