Daily

Observe operating temperature and general conditions. Make sure that the flow of combustion and
intake air to the appliance is not obstructed. Determine the cause of any service codes or lockouts on
®
the NURO
touchscreen display. Observe any unusual noises or operating conditions and make the
necessary corrections. Notify responsible individuals for required corrective action or repair.

Weekly

Observe the conditions of the main flame. A normal high fire flame is mostly blue, though the refractory
in the rear of the heat exchanger will glow an orange red color. A normal low fire flame is also blue.
The refractory may not show any orange-red color at low fire. Never attempt to adjust the flame "by
eye". The correct flame/combustion is dependent on the air and gas adjustment.
Correct air adjustment is essential to the efficient operation of this appliance. Ensure that the flow of
combustion and ventilation air is not obstructed. If an adjustment in the combustion appears
necessary, the flue gas composition should be checked with a combustion analyzer and compared to
the values stated in the Combustion Setup and Adjustment combustion settings table in 3.11.2. If an
adjustment to the combustion is necessary, call a qualified and knowledgeable installer or service
agency that has been trained on the Patterson-Kelley appliance.

Monthly

1. Press the "Info" button on the NURO
down to view the flame signal measured in Volts. Typical flame signals should read between 8-
25V.
2. Test the low water level cut-off. Refer to
3. Test the manual reset high-temp limit. Refer to 3.10.4.
4. Test the low gas pressure switch. Refer to 3.10.5.
5. Test operating temperature controls by reducing or increasing temperature settings as
necessary to check burner operation.
6. Check the combustion chamber condensate drain piping for leaks or obstructions.
NOTICE! Installation and service must be performed by a qualified installer or service agency that
has been trained on the appliance.
Outdoor Boilers
1.
Check for flue gas recirculation into the air inlet. Flue gas recirculation indicates that the vent is
not installed properly for local conditions.
2.
Check for freezing of the condensate lines. Frozen lines will result in boiler malfunction.
Operation of the boiler in cold temperatures may require the use of heat trace lines for the boiler
condensate trap and drain.
3.
Check for inlet air box, vent and safety relief valve obstructions due to outdoor debris such as
but not limited to, leaves, insects, snow, branches and other blockages.
Revised: October 2, 2019
Released: October 2, 2019
Check daily to be sure that the
immediate area around the boiler or
water heater is free and clear of any
combustible materials, including
flammable vapors and liquids.
®
touchscreen to load the Information Screen and scroll
 Patterson-Kelley 2019
All Rights Reserved.
Technical Service 1.877.728.5351
3.10.2
(if applicable).
2691000099 P-K Storm Installation and Owners
P-K Storm
TM
Gas Fired Boiler
Manual.docx
Page 53

Advertisement

Table of Contents
loading

This manual is also suitable for:

P-k storm st-1500P-k storm st-2000P-k storm st-1750

Table of Contents