Manual Control Mode For High And Low Fire Adjustment - Patterson-Kelley P-K STORM ST-1250 Installation & Owner's Manual

Gas fired boiler w/ nuro control system. natural gas boilers
Table of Contents

Advertisement

Manual Control Mode for High and Low Fire Adjustment

To adjust/tune combustion, use the NURO's "Manual Control Firing Rate" mode. To access this mode,
touch the "Info" button in the lower left corner of the screen, and then press "Service" in the lower left.
Next, touch "Press to Activate Manual Control" which will open the "Manual Control Firing Rate" mode.
This test mode should be used when adjusting or tuning the gas safety shut off/control valve.
NOTE: Proper water flow should be established before performing any combustion adjustments to
ensure the boiler doesn't short-cycle or overheat.
Once in "Manual Control Firing Rate" mode, a heat request is required. Once the appliance cycles on
and is running in "Manual Control Firing Rate", use the UP and DOWN arrows or the slider to force the
boiler to operate at low fire, high fire, or anywhere in-between. To prevent the appliance from cycling
off prematurely during adjustment, ensure that any load devices (air handlers, control valves, radiators,
air handling units, etc.) are in operation and are able to shed/dump the heat created by the boiler.
Recommended Combustion Settings for P-K STORM Boilers
Fuel
Natural Gas
The P-K Storm
boilers are equipped with a combination gas/air control and gas safety shut off control
valve. The "zero governor" gas valve responds to the variable speed combustion blower in order to
supply the correct air/gas ratio for optimum performance and efficiency.
NOTICE! For high altitude adjustments (greater than 2,000 feet above sea level), see
– Boiler Altitude Derate Schedule
Revised: October 2, 2019
Released: October 2, 2019
Nominal Gas Pressure
7" W.C.
at the end of this manual.
 Patterson-Kelley 2019
All Rights Reserved.
Technical Service 1.877.728.5351
High Fire Setting
% O
% CO
% O
2
2
8.3 - 8.7
6.3 - 5.7
6.3 - 5.7
2691000099 P-K Storm Installation and Owners
P-K Storm
TM
Gas Fired Boiler
Low Fire Setting
% CO
2
2
8.0 - 8.5
Appendix B
Manual.docx
Page 45

Advertisement

Table of Contents
loading

This manual is also suitable for:

P-k storm st-1500P-k storm st-2000P-k storm st-1750

Table of Contents