Setup Wizard

The Setup Wizard is recommended for all boilers and water heaters
because it guides the user through setup for multiple applications
(Standalone Comfort Heat, Standalone Domestic How Water, and/or
Cascade operation). The Setup Wizard will guide the user through the
parameter setup for all the relevant applications based on responses
to a series of questions. To access the Setup Wizard, press <SETUP
WIZARD> from the "SETTINGS" menu.
While navigating the Setup Wizard, press the desired buttons in the
center content area. The selected choice will be indicated with a
yellow light as seen below. To proceed to the next Setup Wizard
screen, press <NEXT> at the bottom of the screen. The NURO
control also allows the user to back-track at any time by pressing
<PREVIOUS> in the bottom-left corner of the screen.
The Setup Wizard allows the user to assign functionality to the user-
configurable Relays A through D. This allows the user to assign
functions like "Boiler Pump", "System Pump", "Flame Detected", and
"Air Damper" to the relays.
NOTE: The relay assignments must agree with the wiring to/from the appliance. For example, if
Relay A is user-configured to enable/disable the Boiler Pump, the control wires to operate the boiler
pump must be properly wired to the Relay A terminals in the High Voltage (TB2) terminal block.

3.13 Typical Boiler Operating Conditions

Model
Input Rating
Number
(BTU/Hr)
ST-1250
1,250,000
ST-1500
1,500,000
ST-1750
1,750,000
ST-2000
2,000,000
Revised: October 2, 2019
Released: October 2, 2019
Voltage
Phase
208-240
Single
208-240
Single
208-240
Single
208-240
Single
 Patterson-Kelley 2019
All Rights Reserved.
P-K Storm
Technical Service 1.877.728.5351
®
Gas Flow Rate
(CFH)
Total
Natural
Amperage
Gas
(1030 Btu/ft^3)
Less than 10
1214
Less than 10
1456
Less than 20
1699
Less than 20
1942
2691000099 P-K Storm Installation and Owners
TM
Gas Fired Boiler
Output
Capacity
(Btu/Hr)
1,212,500
1,455,000
1,697,500
1,940,000
Manual.docx
Page 49