Carrier Frequency Setting Error (oPE11)

A carrier frequency setup error (oPE11) will occur when carrier frequency gain (C6-05) is
greater than 6 and C6-03 < C6-04.
Note:
Refer to Troubleshooting without Fault Display on page 228
(oPE).

Carrrier Frequency and Drive Overload Current Level

With C6-01 set to 1, the carrier frequency setting defines drive output current level.
Table 4.19 Current Derating by Carrier Frequency Setting
Single-Phase 200 V
Carrier
Model
Frequency
(Capacity)
(kHz)
2
B 0001
0.2 kW/
10
0.1 kW
15
2
B 0002
0.4 kW/
10
0.2 kW
15
2
B 0003
0.75 kW/0.4
10
kW
15
2
B 0006
1.1 kW/0.75
10
kW
15
2
B 0010
2.2 kW/
8
1.5W
15
2
B 0012
3.0 kW/
8
2.2 kW
15
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
Three-Phase 200 V
Output
Model
Current
Frequency
(Capacity)
(A)
1.2
2 0001
0.8
0.2 kW/
0.1 kW
0.6
1.9
2 0002
1.6
0.4 kW/
0.2 kW
1.3
3.3
2 0004
3.0
0.75 kW/0.4
kW
2.4
6.0
5.0
4.0
2 0006
1.1 kW/
0.75W
2 0008
1.5 kW/
1.1 kW
9.6
2 0010
8.0
2.2 kW/
1.5W
6.4
12.0
2 0012
11.0
3.0 kW/
2.2 kW
8.8
4.6 Basic Drive Setup Adjustments
for information on operator errors
Carrier
Output
Model
Current
(Capacity)
(kHz)
(A)
2
1.2
10
0.8
15
0.6
2
1.9
4 0001
10
1.6
0.4 kW/
0.2 kW
15
1.3
2
3.3
4 0002
10
3.0
0.75 kW/0.4
15
2.4
4 0004
1.5 kW/0.75
2
6.0
10
5.0
15
4.0
2
8.0
8
6.9
15
5.5
2
9.6
4 0005
8
8.0
2.2 kW/
1.5W
15
6.4
2
12.0
4 0007
8
11.0
3.0 kW/
2.2 kW
15
8.8
Three-Phase 400 V
Carrier
Output
Frequency
Current
(kHz)
(A)
2
1.2
8
1.2
15
0.7
2
2.1
8
1.8
kW
15
1.1
2
4.1
8
3.4
kW
15
2.0
2
5.4
8
4.8
15
2.9
2
6.9
8
5.5
15
3.3
4
137