Appendix 2.1 Differences In Led Displays And Switch Settings - Mitsubishi Electric Melsec QJ71LP21 Reference Manual

Q corresponding melsecnet/h network system
Hide thumbs Also See for Melsec QJ71LP21:
Table of Contents

Advertisement

APPENDICES
Appendix 2 Differences Between the AJ71QLP21/AJ71QLP21G/AJ71QBR11, the
A1SJ71QLP21/A1SJ71QBR11 and the QJ71LP21/QJ71LP21-25/QJ71LP21G/
QJ71BR11

Appendix 2.1 Differences in LED displays and switch settings

Table 2 Difference of LED indications, switch setting and others
Model name
Item
LED display
Network No. setting
switch
Group No. setting switch
Station number setting
switch
MODE
0: Online
(parameters are valid)
1: Self-loopback test
2: Internal self-loopback test
3: Hardware test
4: Online
Mode setting switch
5: Self-loopback test
6: Internal self-loopback test
7: Hardware test
8: and up: Use prohibited
Display select switch
Condition setting switch
Applicable CPU
Applicable base
98 (3.86) (H)
External dimensions
90 (3.54) (D) [mm (inch)]
Weight
1: The LED display is activated with the display selection switch.
2: The detailed contents of an error code can be checked by the network diagnostics.
3: Set with a network parameter.
4: Only possible with the QJ71LP21-25. Use with the QJ71LP21, QJ71LP21G and QJ71BR11 is prohibited.
App - 5
The MELSECNET/H network modules QJ71LP21, QJ71LP21-25, QJ71LP21G and
QJ71BR11 have the same LED displays and switch settings as those of the
MELSECNET/10 network modules AJ71QLP21, AJ71QLP21G, AJ71QBR11,
A1SJ71QLP21, and A1SJ71QBR11. However, each network module has the following
differences from others as shown in Appendix Table 2. Please consider these
differences when operating the network modules.
QJ71LP21, QJ71LP21-25
QJ71LP21G, QJ71BR21
RUN
MNG
T.PASS
D.LINK
SD
RD
ERR.
2
L ERR.
2
3
3
STATION NO.
10,
1
3
4
4
4
4
3
QCPU
Q3
B, Q6
B
27.4 (1.08) (W)
0.11kg
AJ71QLP21
AJ71QBR11
AJ71QLP21G
RUN
POWER
PC
REMOTE
DUAL
MNG, S.MNG
T.PASS
D.LINK
SD
RD
SW.E.
M/S.E.
PRM.E.
CPU R/W
CRC
OVER
OVER
AB.IF
AB.IF
TIME
TIME
DATA
DATA
UNDER
UNDER
LOOP
NETWORK NO.
100,
10,
1
GROUP NO.
STATION NO.
10,
1
MODE
0: Online
1: Use prohibited
2: Offline (disconnected)
3: Forward loop test
4: Reverse loop test
5: Station-to-station test (master station)
6: Station-to-station test (host)
7: Self-loopback test
8: Internal self-loopback test
9: Hardware test
D: Network No. confirmation
E: Group No. confirmation
F: Station number confirmation
SW1
: PC
REMOTE
SW2
: N.ST
MNG
SW3
: PRM
D.PRM
SW4, 5
: STATION SIZE
SW6, 7
: LB/LW SIZE
Q4ARCPU, QnACPU, Q2ASCPU
A3 B, A5 B, A6 B,
A38HB, A37RHB, A3 RB, A68RB
AJ71QLP21, AJ71QLP21G:
250 (9.84) (H)
37.5 (1.48) (W)
(4.37) (D) [mm (inch)]
AJ71QBR11:
250 (9.84) (H)
37.5 (1.48) (W)
(4.45) (D) [mm (inch)]
0.45kg
A1SJ71QLP21
(REM.)
DUAL
MNG, S.MNG
(SW.E.)
(M/S.E.)
(PRM.E.)
CRC
CRC
OVER
AB.IF
TIME
DATA
UNDER
F.E. (R.E.)
NETWORK NO.
100,
MODE
0: Online
1: Use prohibited
2: Offline (disconnected)
3: Forward loop test
4: Reverse loop test
5: Station-to-station test (master station)
6: Station-to-station test (host)
7: Self-loopback test
8: Internal self-loopback test
9: Hardware test
DISPLAY L
SW1
SW2
SW3
SW4, 5
SW6, 7
A1S3 B, A1S5 B,
A1S6 B, A1S38HB
A1SJ71QLP21:
111
130 (5.12) (H)
(3.69) (D) [mm (inch)]
A1SJ71QBR11:
113
130 (5.12) (H)
(4.12) (D) [mm (inch)]
MELSEC-Q
A1SJ71QBR11
RUN
(PW)
1
(PC)
1
1
T.PASS
D.LINK
SD
RD
1
1
1
CPU R/W
CRC
OVER
AB.IF
TIME
DATA
UNDER
1
10,
1
GR.NO.
ST NO.
10,
1
R
: PC
REM
: N.ST
MNG
: PRM D.
PRM
: STATION SIZE
: LB/LW SIZE
Q2ASCPU
34.5 (1.36) (W)
93.6
34.5 (1.36) (W)
104.6
0.3kg
App - 5

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents