Specifications; Generic Specifications; Power Supply Specifications - Mitsubishi MELSEC-F FX3U Series User Manual

Programmable controllers
Hide thumbs Also See for MELSEC-F FX3U Series:
Table of Contents

Advertisement

FX
/FX
Series PLC User's Manual - Analog Control Edition
3U
3UC
FX
-4AD-TC-ADP (4-channel Thermocouple Data Input)
3U
2.

Specifications

This chapter describes the general, power supply, and performance specifications for TC-ADP.
2.1

Generic Specifications

Item
Ambient temperature 0 to 55°C (32 to 131°F) when operating and -25 to 75°C (-4 to 158°F) when stored
Relative humidity
Vibration resistance
Shock resistance
Noise resistance
Dielectric withstand
voltage
Insulation resistance
Grounding
Working atmosphere Free from corrosive or flammable gas and excessive conductive dusts
Working altitude
*1.
If TC-ADP is connected to the FX
*2.
PLC
Independent grounding
Best condition
*3.
If the pressure is higher than the atmospheric pressure, do not use TC-ADP.
TC-ADP may malfunction.
2.2

Power Supply Specifications

Item
A/D conversion circuit
driving power
Interface driving power
F-6
5 to 95%RH (no condensation) when operating
Compliant with EN 68-2-6
Frequency
DIN Rail Mounting
57 - 150
10 to 57
*1
Direct Mounting
57 to 150
Compliant with EN 68-2-27
2
(147 m/s
Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y,
and Z)
Using noise simulator of:
Noise voltage: 1,000Vp-p / Noise width: 1µs / Rise: 1ns / Cycle: 30 to 100Hz
500 V AC, for 1 min
5MΩ or more using 500V DC
insulation resistance meter
Class D grounding (grounding resistance: 100 Ω or less)
<Common grounding with a heavy electrical system is not allowed.>
Compliant with IEC61131-2 (<2000m)
3UC
Another
Another
PLC
equipment
equipment
Shared grounding
Good condition
→ For a detailed description of the grounding, refer to Section 3.7.
24V DC +20% -15%, 45mA
(It is necessary to connect the 24V DC power supply to the terminal block.)
5V DC, 15mA
(Since the internal power is supplied from the FX Series main unit, it is not
necessary to supply the power.)
Specifications
Acceleration
2
(Hz)
(m/s
)
10 - 57
-
4.9
9.8
(Between batch of all terminals and ground terminal)
Comply with JEM-1201
*3
Series PLC, direct installation is not possible.
Another
PLC
equipment
Common grounding
Not allowed
Specifications
2 Specifications
2.1 Generic Specifications
Half amplitude
(mm)
10 times of testing in
0.035
each direction (X-, Y-,
and Z-axis directions)
-
(Total: 80 min, each)
0.075
*2