Specifications; Generic Specifications - Mitsubishi MELSEC-F FX3U Series User Manual

Programmable controllers
Hide thumbs Also See for MELSEC-F FX3U Series:
Table of Contents

Advertisement

FX
/FX
Series PLC User's Manual - Analog Control Edition
3U
3UC
FX
-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)
3U
2.

Specifications

This chapter describes the general, power supply, and performance specifications for PT-ADP.
2.1

Generic Specifications

Item
Ambient
temperature
Relative
humidity
Vibration
resistance
Shock
resistance
Noise
resistance
Dielectric
withstand
voltage
Insulation
resistance
Grounding
Working
atmosphere
Working
altitude
*1.
If PT-ADP is connected to the FX
*2.
PLC
Independent grounding
Best condition
*3.
If the pressure is higher than the atmospheric pressure, do not use PT-ADP.
PT-ADP may malfunction.
E-6
0 to 55°C (32 to 131°F) when operating and -25 to 75°C (-4 to 158°F) when stored
5 to 95%RH (no condensation) when operating
Compliant with EN 68-2-6
Frequency
(Hz)
10 - 57
DIN Rail Mounting
57 - 150
10 to 57
Direct Mounting
*1
57 to 150
Compliant with EN 68-2-27
2
(147 m/s
Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z)
Using noise simulator of:
Noise voltage: 1,000Vp-p / Noise width: 1µs / Rise: 1ns / Cycle: 30 to 100Hz
500 V AC, for 1 min
5MΩ or more using 500V DC
insulation resistance meter
Class D grounding (grounding resistance: 100 Ω or less)
<Common grounding with a heavy electrical system is not allowed.>
Free from corrosive or flammable gas and excessive conductive dusts
Compliant with IEC61131-2 (<2000m)
3UC
Another
PLC
equipment
Shared grounding
Good condition
→ For a detailed description of the grounding, refer to Section 3.6.
Specifications
Acceleration
2
(m/s
)
-
4.9
9.8
(Between batch of all terminals and ground terminal)
Comply with JEM-1201
*3
Series PLC, direct installation is not possible.
Another
Another
PLC
equipment
equipment
Common grounding
Not allowed
2 Specifications
2.1 Generic Specifications
Half amplitude
(mm)
10 times of testing in
0.035
each direction (X-, Y-,
and Z-axis directions)
-
(Total: 80 min, each)
0.075
*2