PID Instruction (FNC 88)
3.2

Details of Parameters

3.2.1
Sampling time (T
Set the cycle time (ms) for the PID operation.
• In the PID control
Set the sampling time longer than the operation cycle of the PLC.
• In the auto tuning
Set the sampling time to 1,000 ms (= 1 second) or more.
1. Maximum error
The maximum error of the sampling time (T
cycle)."
1) When the sampling time (T
Fluctuation of the maximum error described above may cause a problem.
In such a case, execute PID instruction in the constant scan mode, or program it in a timer interrupt
routine.
2) When the sampling time is shorter than one operation cycle of the PLC
A PID operation error (K6740) occurs, but the PID operation is executed while the sampling time (T
equal to the operation cycle of the PLC.
In such a case, use PID instruction in a timer interrupt (I6
executing PID instruction.
→ For a detailed description, refer to FX
X000
I610
): (S3)
S
) is from "-(one operation cycle + 1 ms)" to "+(one operation
S
) is a small value
S
FNC 12
K 0
D107
MOVP
FNC 88
D 0
D 1
PID
Setting range: 1 to 32767 [ms]
to I8
/FX
Series Programming Manual - Basic & Applied
3U
3UC
S
3
+7 is reset.
(When the interrupt routine is executed for the
first time,the register for internal processing is
cleared by the pulse generation command.)
The PID operation is
D100
D150
executed.
3 Parameter
3.2 Details of Parameters
), and clear
+7 just before
S
3
Instruction Edition
G-9
A
B
C
D
) is
S
E
F
G