Parameter; Parameter List: (S3) To (S3) + 28 - Mitsubishi MELSEC-F FX3U Series User Manual

Programmable controllers
Hide thumbs Also See for MELSEC-F FX3U Series:
Table of Contents

Advertisement

FX
/FX
Series PLC User's Manual - Analog Control Edition
3U
3UC
PID Instruction (FNC 88)
3.

Parameter

This chapter describes various parameters of PID instruction.
3.1

Parameter List: (S3) to (S3) + 28

Set item
Sampling time (T
S
S
3
3
Operation
+1
S
S
3
3
setting (ACT)
Input filter constant (α)
+2
S
S
3
3
Proportional gain (K
+3
S
S
3
3
Integral time (T
)
I
S
S
+4
3
3
Differential gain (K
S
S
+5
3
3
Differential time (T
S
S
+6
3
3
S
S
+7
3
3
:
These devices are occupied for internal processing of PID operation. Do not change data.
S
S
+19
3
3
Setting
)
1 to 32767 (ms)
S
0: Forward operation
bit0
1: Backward operation
0: Input variation alarm is invalid.
bit1
1: Input variation alarm is valid.
0: Output variation alarm is invalid.
bit2
1: Output variation alarm is valid.
bit3
Not available
0: Auto tuning is not executed.
bit4
1: Auto tuning is executed.
0: Upper and lower limits of output
value are not valid.
bit5
1: Upper and lower limits of output
value are valid.
0: Step response method
bit6
1: Limit cycle method
bit7 to bit15
Not available
0 to 99 (%)
)
1 to 32767 (%)
P
0 to 32767 (× 100 ms)
)
0 to 100 (%)
D
)
0 to 32767 (× 10 ms)
D
3.1 Parameter List: (S3) to (S3) + 28
Remarks
It cannot be shorter than operation
cycle.
Operation direction
Do not set to ON bit 2 and bit 5 at
same time.
Do not set to ON bit 2 and bit 5 at
same time.
Select auto tuning mode.
When "0" is set, input filter is not
provided.
When "0" is set, it is handled as "∞"
(no integration).
When "0" is set, differential gain is
not provided.
When "0" is set, differential is not
executed.
3 Parameter
A
B
C
Reference
Subsection
3.2.1
D
Subsection
3.2.2
E
F
Subsection
3.2.3
Subsection
3.2.4
Subsection
3.2.5
G
Subsection
3.2.6
Subsection
3.2.7
G-7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents