3. Wiring
WIRING
PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
WIRING
PRECAUTIONS
• When drilling screw holes or wiring, make sure cutting or wire debris does
not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to observe the following precautions in order to prevent
malfunctions under the influence of noise:
1) Do not bundle the power line or shield of the analog input/output cable
together with or lay it close to the main circuit, high-voltage line, or load
line.
Otherwise, noise disturbance and/or surge induction are likely to take
place. As a guideline, lay the control line at least 100mm (3.94") or more
away from the main circuit, high-voltage line, or load line.
2) Ground the shield of the analog input/output cable at one point on the
signal receiving side. However, do not use common grounding with heavy
electrical systems.
• Make sure to properly wire to the terminal block (European type) in
accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit,
wire breakage, malfunctions, or damage to the product.
- The disposal size of the cable end should follow the dimensions
described in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires
of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected
parts are directly stressed.
• Make sure to properly wire the terminal block in accordance with the
following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit,
wire breakage, malfunctions, or damage to the product.
- The disposal size of the cable end should follow the dimensions
described in the manual of the PLC main unit.
- Tightening torque should follow the specifications in the manual of the
PLC main unit.
3.1 Applicable cable and terminal tightening torque
3.1.1
Type terminal block (European type)
1) Wire size
- The power supply wiring and the Type K/J changeover input wiring should
use 22-20 AWG wire.
- Thermocouple wiring should use the compensating lead wire suitable for
the type of thermocouple.
→ For details of compensating lead wire, Refer to Section 3.3
2) Applicable cable
Type
Wire size
Single-wire
2
2
0.3 mm
to 0.5 mm
(AWG22 to 20)
2-wire
2
2 pieces of 0.3 mm
(AWG22)
3) Termination of cable end
Strip the coating of strand wire and twist the cable core before connecting it,
or strip the coating of single wire before connecting it.
An alternative connection is to use a ferrule with insulating sleeve.
<Reference>
Manufacturer
Model
Caulking tool
CRIMPFOX 6
Phoenix Contact Co., Ltd.
AI 0.5-8WH
(or CRIMPFOX 6T-F
*1 Old model name: CRIMPFOX ZA 3
*2 Old model name: CRIMPFOX UD 6
- Strand wire/single wire
- Stick terminal with insulating sleeve
Insulation sleeve
Contact area
(Crimp area)
9mm
(0.35")
2.6mm(0.1")
14mm(0.55")
When using a stick terminal with insulating sleeve, choose a wire with proper
cable sheath referring to the above outside dimensions, or otherwise, the wire
cannot be inserted easily. The tightening torque must be 0.22 to 0.25 N
not tighten terminal screws exceeding the specified torque. Failure to do so
may cause equipment failures or malfunctions.
3.2 Power Supply Wiring
For the power supply wiring, refer to the following manual.
→ FX
/FX
/FX
/FX
/FX
Series User's Manual - Analog Control Edition
3S
3G
3GC
3U
3UC
3.3 Selection of thermocouple
→ For the terminal configuration, refer to Section 1.2
Precautions on thermocouple wiring
• Thermocouple type
- There are 2 types of thermocouples: Type K and Type J. Select the desired type.
However, be sure to connect the same type of thermocouple to all the channels.
- Use insulated thermocouple types.
• Compensating lead wire
Thermocouple
Type of compensating lead wire
To connect the
thermocouple, use one of
Type K
KX, KCA, KCB, KCC
the right types of
compensating lead wires.
Type J
JX
The compensating lead
w i r e
i n d i c a t e s
t h e
temperature value of approximately 0.12 °C higher than that of the wire resistor (10
Ω). Temperature value should be used in consideration of this point.
If the compensating lead wire is very long, the wire may be easily affected by noise,
etc. It is, therefore, recommended that the length of the compensating lead wire
should be 100 m (328' 1") or less.
Example of thermocouple wiring
Terminal
Using Type J
block
J-type
*1
J-type
Thermocouple Wiring
Compensating lead
Thermocouple
wire (Shielded)
L +
L
-
L +
L
-
External power
supply wiring
24+
24 V DC
24-
*2
Grounding
(Ground resistance: 100 Ω or less)
L +, L -, ch
:
represents the channel number.
*1 When using the Type J thermocouple, short-circuit the 'Type J' terminals and turn
the special auxiliary relay (Type K/J mode changeover) ON.
For details of auxiliary relays, refer to the following manual.
→ FX
/FX
/FX
/FX
/FX
Series User's Manual - Analog Control Edition
3S
3G
3GC
3U
3UC
*2 24 V DC service power supply of the FX
3S
/FX
3G
used.
3.4 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100 Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" of the
following figure.
For details, refer to the respective PLC User's manual Hardware Edition.
Other
Other
PLC
PLC
equipment
equipment
Independent grounding
Shared grounding
Best condition
Good condition
• The grounding wire size should be AWG 22-20 (0.3-0.5 mm
• The grounding point should be close to the PLC, and all grounding wire should be
*1
as short as possible.
*2
)
8mm
(0.31")
m. Do

4. Specifications

STARTUP AND
MAINTENANCE
PRECAUTIONS
• Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
* For repair, contact your local Mitsubishi Electric representative.
• Do not drop the product or exert strong impact to it.
Doing so may cause damage.
DISPOSAL
PRECAUTIONS
• Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
TRANSPORTATION AND
STORAGE PRECAUTIONS
• The product is a precision instrument. During transportation, avoid any impacts.
Failure to do so may cause failures in the product. After transportation, verify the
operations of the product.
TC-ADP
4.1 Applicable PLC
Model name
Temperature
FX
3S
Series PLC
Ver. 1.00 or later (from first production)
compensation circuit
FX
Series PLC
Ver. 1.00 or later (from first production)
3G
3kΩ
ch
FX
Series PLC Ver. 1.40 or later (from first production)
3GC
FX
3U
Series PLC
Ver. 2.20 or later (from first production)
Ver. 1.30 or later (from the production manufactured in August,
FX
3UC
Series PLC
Temperature
2004 with SER No. 48****)
compensation circuit
3kΩ
The version number can be checked by monitoring D8001/D8101 as the last three
ch
digits indicate it.
4.2 General Specifications
+5V
Items other than the following are equivalent to the those of the PLC main unit.
For general specifications, refer to the respective PLC User's manual Hardware
Edition.
Item
Dielectric withstand
500 V AC for one minute
voltage
5 M Ω o r m o r e b y 5 0 0 V D C
Insulation resistance
megger
4.3 Power Supply Specifications
/FX
3U
Series PLC can also be
Item
A/D conversion
24 V DC +20 %/-15 %, 45 mA for 24 V DC
circuit driving power
Connect a 24 V DC power supply to the terminal block.
5 V DC, 15 mA
Interface driving
5 V DC power is supplied from the internal power supply of
power
main unit.
Other
PLC
equipment
Common grounding
Not allowed
2
).
4.4 Performance Specifications
Item
Input signal
Type K -100 ° C to +1000 ° C Type K -148 ° F to +1832 ° F
Rated
temperature
Type J
range
Type K
Digital output
Type J
Type K
Resolution
Type J
Total accuracy
• FX
A/D conversion
(The data will be updated at every scan time of the PLC.)
time
• FX
(The data will be updated at every scan time of the PLC.)
Type K
Applicability
+10100
+10000
-100°C
Input
characteristics
Type J
-100°C
Specification
• The photocoupler is adopted to insulate the analog input
Between all terminals and
area from the PLC.
ground terminal of PLC
Insulation
• The DC/DC converter is adopted to insulate the power
main unit
method
supply line from the analog input area.
• A channels are not insulated from each other.
Occupied
0 point (This number is not related to the maximum number of
Specification
points
input/output points of the PLC.)
This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Mitsubishi will not be held liable for damage caused by factors found not to be
the cause of Mitsubishi; opportunity loss or lost profits caused by faults in the
Mitsubishi products; damage, secondary damage, accident compensation
caused by special factors unpredictable by Mitsubishi; damages to products
other than Mitsubishi products; and to other duties.
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Specifications
Centigrade ( ° C)
Fahrenheit ( ° F)
Thermocouple type K or J
JIS C 1602-1995
-100 ° C to +600 ° C
-148 ° F to +1112 ° F
Type J
-1000 to +10000
Type K
-1480 to +18320
-1000 to +6000
Type J
-1480 to +11120
0.4 ° C
0.72 ° F
Type K
0.3 ° C
0.54 ° F
Type J
±(0.5 % full scale +1 ° C)
Series PLC: 200 μs
3U
/FX
3UC
Series PLC: 250 μs
3S
/FX
3G
/FX
3GC
Type K
+18500
+18320
°
0
-148
F
0
+1000°C
°
+1832
F
-1000
-1480
-1100
-1660
Type J
+6100
+11300
+6000
+11120
°
0
-148
F
0
+600°C
°
+1112
F
-1000
-1480
-1100
-1660
For safe use