Installing the Cisco NCS 4216
Installing Plenum Assembly and Chassis in the Rack
Following steps help you to install the plenum assembly irrespective of the chassis and rack size.
Note
The below illustrations are for representation purpose only. The size displayed in the images may vary
depending upon your chassis type and rack size but the steps remain the same. Ensure to select the 21 or 23
inches adapter for your plenum based on your rack size.
Procedure
Step 1
Position the adapter to the plenum base and secure using a maximum torque of 11.5 in.-lb (1.3 N-m). See
figure below.
Figure 2: Adapter to Plenum
1
3
Step 2
Position the air deflector inside the plenum and secure using a maximum torque of 11.5 in.-lb (1.3 N-m). See
figure below.
Plenum adapter deflector
Securing the Plenum to the base
Installing Plenum Assembly and Chassis in the Rack
2
Plenum
-
Installing the Cisco NCS 4216
3