5 Diagnostics
5.5 CFC test mode
The following table shows further connection properties of the OR_M_16C:
Table 5–1
Connection
MODE1_xx
Channel operating mode (xx = 00 – 07 / 00 – 15)
of the primary module
MODE2_xx
Channel operating mode (xx = 00 – 07 / 00 – 15)
of the redundant module
OMODE_xx
Channel operating mode (xx = 00 – 07 / 00 – 15)
QDISCREP
1 = expired discrepancy time
QMODF1
1 = error in module 1
QMODF2
1 = error in module 2
Note
Further information about the connections of the OR_M_16 and its fault
messages can be found in the manual "SIMATIC Process Control System PCS 7
Basic Library (V8.1)".
Examples of the value status
Byte 3:
16#80: Value status "valid value"
16#00: Value status "invalid value" (channel fault)
16#40: Value status "invalid value" (higher-level fault)
Byte 2:
16#01: Restart (OB 100) done
16#02: Above measuring range (channel fault diagnostics)
16#04: Below measuring range (channel fault diagnostics)
Configuration of Redundant I/O Modules
Entry-ID: 28430682,
V2.0,
Meaning
03/2015
Data Type
Default
Setting
DWORD
0
DWORD
0
DWORD
0
BOOL
0
BOOL
0
BOOL
0
Type
I
I
O
O
O
O