3 Configuring the redundant peripherals
3.9 CFC configuration
Activity
4.
Click on the relative symbol with which you
want to connect the block.
You can select between the symbols that
you assigned in the HW Config during the
symbol assignment (see chapter 3.8).
5.
In the final compilation, the module drivers
are automatically generated for the
corresponding blocks. It is important to
make sure that the field "Generate module
drivers" is selected in the dialog window
"Compile program".
6.
As a result, the terminals MS, MODE,
DataXchg, DataXchg1 and MS_Xchg of the
channel block are connected automatically
to the @-plans, generated by the system.
Configuration of Redundant I/O Modules
Entry-ID: 28430682,
V2.0,
03/2015
Screenshot
59