3 Configuring the redundant peripherals
3.5 Signal module settings
Activity
7.
The redundant signal modules are now
listed in the "Module Overview" field.
You can also set additional parameters
(see chapter 3.6 Additional parameter
settings for the configuration of the
redundant AI modules").
These additional parameters can only be
set for the input modules DI and AI. Click
the "OK" button to apply the settings.
By clicking the "Help" button you can get
further information about each parameter.
8.
Repeat steps 1 to 7 for all the signal
modules you wish to connect redundantly.
Configuration of Redundant I/O Modules
Entry-ID: 28430682,
V2.0,
03/2015
Screenshot
50