Omron CJ-Series Operation Manual page 117

Built-in i/o. cpu units
Hide thumbs Also See for CJ-Series:
Table of Contents

Advertisement

Built-in Outputs
Independent Mode
(Positioning)
Operation
Example
application
Output with
Positioning
specified
without accel-
speed
eration or
deceleration
Simple trap-
Positioning
ezoidal con-
with trapezoi-
trol
dal accelera-
tion and
deceleration
(Same rate
used for
acceleration
and decelera-
tion; no start-
ing speed)
The number
of pulses can-
not be
changed dur-
ing position-
ing.
Complex
Positioning
trapezoidal
with trapezoi-
control
dal accelera-
tion and
deceleration
(Separate
rates used for
acceleration
and decelera-
tion; starting
speed)
The number
of pulses can-
not be
changed dur-
ing position-
ing.
98
Starting a Pulse Output
Frequency changes
Specified number of
Pulse frequency
pulses (Specified with
PULS(886).)
Target
frequency
Execution of
Outputs the specified
SPED(885)
number of pulses
and then stops.
Specified number of
Pulse frequency
pulses (Specified
with PULS(886).)
Target
Acceleration/
frequency
deceleration
rate
Execution of
Outputs the specified
ACC(888)
number of pulses and
then stops.
Pulse frequency
Specified number
of pulses
Target
frequency
Acceler-
ation
rate
Starting
frequency
Execution of
PLS2(887) Target
Deceleration point
frequency
reached.
Note Triangular Control
If the specified number of pulses is less than the number required just to
reach the target frequency and return to zero, the function will automatically
Description
Starts outputting
pulses at the speci-
fied frequency and
stops immediately
when the specified
number of pulses
has been output.
Time
Note The target
position
(specified
number of
pulses) can-
not be
changed dur-
ing position-
ing.
Accelerates and
decelerates at the
same fixed rate and
stops immediately
when the specified
number of pulses
has been output.
(See note.)
Time
Note The target
position
(specified
number of
pulses) can-
not be
changed dur-
ing position-
ing.
Accelerates and
decelerates at a
fixed rates. The
pulse output is
Deceleration
stopped when the
rate
specified number of
pulses has been
Stop
output. (See note.)
frequency
Time
Note The target
Output stops.
position
(specified
number of
pulses) can
be changed
during posi-
tioning.
Section 5-2
Procedure
Instruction
Settings
•Number
PULS(886)
of pulses
•Relative
SPED(885
or abso-
lute pulse
specifica-
tion
•Port
•"CW/
CCW" or
"Pulse +
direction"
•Indepen-
dent
•Target fre-
quency
PULS(886)
•Number
of pulses
•Relative
ACC(888)
(Indepen-
or abso-
dent)
lute pulse
specifica-
tion
•Port
•"CW/
CCW" or
"Pulse +
direction"
•Indepen-
dent
•Accelera-
tion and
decelera-
tion rate
•Target fre-
quency
PLS2(887)
•Number
of pulses
•Relative
or abso-
lute pulse
specifica-
tion
•Port
•"CW/
CCW" or
"Pulse +
direction"
•Accelera-
tion rate
•Decelera-
tion rate
•Target fre-
quency
•Starting
frequency

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj1m-cpu22Cj1m-cpu23

Table of Contents