Siemens RUGGEDCOM RST2228 Installation Manual page 47

Table of Contents

Advertisement

RUGGEDCOM RST2228
Installation Guide
Test
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-10
IEC 61000-4-11
IEC 61000-4-16
IEC 61000-4-17
IEC 61000-4-18
IEC 61000-4-29
IEC 60255-27
EMC and Environmental Type Tests
Description
Surge
Induced (Conducted) RFI
Magnetic Field
Damped Oscillating
Magnetic Field
Voltage Dips
and Interrupts
Mains Frequency Voltage
Ripple on DC
Power Supply
Damped Oscillatory Wave
Voltage Dips
and Interrupts
Dielectric Strength
DC Power Ports
± 4 kV at 2.5 and 5 kHz
AC Power Ports
± 4 kV at 2.5 and 5 kHz
Earth Ground Ports
Signal Ports
± 4 kV Line-to-Earth
± 2 kV Line-to-Line
DC Power Ports
± 2 kV Line-to-Earth,
± 1 kV Line-to-Line
AC Power Ports
± 4 kV Line-to-Earth
± 2 kV Line-to-Line
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Enclosure Ports
100 A/m for 3 min
Enclosure Ports
100 A/m for 1 s (100
AC Power Ports
60% for 50 periods
100% for 5 periods
100% for 50 periods
Signal Ports
DC Power Ports
AC Power Ports
DC Power Ports
Signal Ports
2.5 kV Common Mode
DC Power Ports
2.5 kV Common Mode
1.0 kV Differential Mode
AC Power Ports
2.5 kV Common Mode
1.0 kV Differential Mode
DC Power Ports
Signal Ports
Test Levels
Severity Levels
± 4 kV at 5 kHz
10 V
10 V
10 V
10 V
1000 A/m for 1 s
kHz and 1 MHz)
30% for 1 period
30 V for 60 s
300 V for 1 s
30 V for 60 s
300 V for 1 s
30 V for 60 s
300 V for 1 s
15%
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
2 kV (Fail-Safe
Relay Output)
Chapter 6
Certification
4
4
4
4
3
4
3
3
3
3
5
5
4
4
4
3
3
3
3
41