Door Incl. Pmi Fhd3601-Z1 - Siemens FC361 Series Technical Manual

Fire control panel
Hide thumbs Also See for FC361 Series:
Table of Contents

Advertisement

Installation
5
Spare Parts

5.12.2 Door incl. PMI FHD3601-Z1

54 | 124
Building Technologies
Fire safety
The door incl. PMI FHD3601-Z1 is already mounted in the fire control panel in the
factory and only has to be replaced in the event of a repair.
Figure 25: Installation of door incl. PMI
Figure 26: Details view of installation
1
Bolt
2
Bolt pin
3
Hinge
w The power supplies (mains and battery) are disconnected.
w Connector to mainboard is disconnected.
w The old door incl. PMI is removed. Refer to document A6V10449593, see
chapter 'Applicable documents [➙ 9]'.
1. From the right side insert the bolt pin on the door into the hinge (3) on the rear
panel, aligning the hole on the bolt pin (2) with the hole on the hinge (3).
2. Secure the door with two bolts (1).
3. Insert the connector to the mainboard into the PCB board on the door.
The panel recovers the previous status after the new door incl. PMI is replaced.
A6V10421795_en--_g
2016-11-18

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fc361-zzFc361-zaFc361-yzFc361-ya

Table of Contents