9.6 Update firmware

Building Technologies
Fire safety
WARNING
Fire detection installation is deactivated during the firmware update
Fire may spread unhindered.
Supervision by people is required.
Re-activate the fire detection installation as soon as possible.
When the panel firmware is updated, the firmware of output card (4M) (if installed)
and the detection module are also updated automatically.
NOTICE
Firmware update on the panel
The configuration of the panel may be affected depending on the update type!
Create backup of the configuration data for the panel before updating
firmware. See chapter 'Appendix C: Flash file behaviors [➙ 116]'.
w Ensure that the latest firmware version is installed on the PC. The latest
firmware version ('FC360 Desktop Editor') is installed on the PC.
1. Connect PC to the panel. Refer to chapter 'Connect PC to panel [➙ 95]'.
2. Set Windows firewall. Refer to chapter 'Set Windows firewall [➙ 101]'.
3. Enter access level 3 password to login to level 3 on panel.
4. Open 'FC360 Desktop Editor'.
5. Click 'Update Firmware'.
a The panel starts to update firmware.
a A successful message is indicated. Otherwise, a failure message is
indicated.
6. Check the version on the panel. See menu item 'About'.
7. Disconnect PC from the panel.
Detailed information about updating firmware is available in document
A6V10450595. See chapter 'Applicable documents [➙ 9]'.
To update the firmware of FT2010 / FT2011 / FDUL221, please refer to the
document A6V10210416. See chapter 'Applicable documents [➙ 9]'.
Commissioning
9
Update firmware
103 | 124
A6V10421795_en--_g
2016-11-18