Table 9 - Refrigerant Liquid Temperature Valve Capacity Multiplier Correction Factors

0
R-12
1.60
Correction Factor
R-134a
1.70
Correction Factor
R-22
1.56
Correction Factor
R-404A/R-507
2.00
Correction Factor
These factors include corrections for liquid refrigerant density and net refrigerating effect and are based on an
average evaporator temperature of 0°F. However, they may be used for any evaporator temperature from - 40°F to
+ 40°F since the variation in the actual Factors across this range is insignificant.
Application
XJAL(Low Temp)
XJAM(Medium
Temp)
© 2017 Emerson Climate Technologies, Inc.
Refrigerant Liquid Temperature °F
10
20
30
40
1.54
1.48
1.42 1.36 1.30
1.63
1.56
1.49 1.42 1.36
1.51
1.45
1.40 1.34 1.29
1.90
1.80
1.70 1.60 1.50

Table 10 - Pressure Control Settings for SJAL/M Units

Control
R-404A/R-507
Low Pressure
Low Pressure
17 PSIG min.
50
60
70
80
1.24 1.18 1.12 1.06
1.29 1.21 1.14 1.07
1.23 1.17 1.12 1.06
1.40 1.30 1.20 1.10
R-407A
0 PSIG min.
26.9 PSIG min.
28
AE5-1377 R3
90
100
110
120
1.00
0.94
0.88
1.00
0.93
0.85
1.00
0.94
0.88
1.00
0.90
0.80
R-407C
N/A
N/A
9.4 PSIG min.
130
140
0.82
0.75
0.78
0.71
0.82
0.76
0.70
0.50