10. Refrigerant Liquid Temperature Valve Capacity Multiplier Correction Factors
Refrigerant Liquid Temperature Entering TXV
0
10
R-22
1.56
1.51
R-404A
2.00
1.90
R-507
2.00
1.90
R-134a
1.70
1.63
R-407A
1.75
1.68
R-407C
1.69
1.62
These factors include corrections for liquid refrigerant density and net refrigerating effect and are based on an
average evaporator temperature of 0°F. However, they may be used for any evaporator temperature from - 40°F
to + 40°F since the variation in the actual factors across this range is insignificant.