Emerson XJAL-020Z-CFV-012 Manual page 38

Outdoor refrigeration unit
Table of Contents

Advertisement

14. DEFAULT SETTING VALUES
Label
Name
rtc Real time clock menu
CF Temperature measurement unit
rES Resolution
EdF Defrost mode
IdF Interval between defrost cycles
MdF (Maximum) length for defrost
dFd Displaying during defrost
dAd MAX display delay after defrost
Fdt Draining time
Hur Current hour
Min Current minute
dAY Current day
Hd1 First weekly holiday
Hd2 Second weekly holiday
st
Ld1 1
workdays defrost start
Ld2 2
nd
workdays defrost start
Ld3 3
rd
workdays defrost start
Ld4 4
th
workdays defrost start
Ld5 5
th
workdays defrost start
th
Ld6 6
workdays defrost start
Sd1 1
st
holiday defrost start
nd
Sd2 2
holiday defrost start
Sd3 3
rd
holiday defrost start
Sd4 4
th
holiday defrost start
Sd5 5
th
holiday defrost start
Sd6 6
th
holiday defrost start
Adr Serial address
onF on/off key enabling
rEL Software release
Ptb Map code
1598030330 XR30CX MRS GB r2.0 23.05.2013.doc
Range
Default Menu
-
-
Pr1
°F
Pr2
°C  °F
in=integer; dE= dec.point
in
Pr2
rtc - in
in
Pr1
8
Pr1
1  120 ore
0  255 min
45
Pr1
rt, it, SEt, DEF
dEF
Pr2
0 ÷ 255 min
0
Pr2
0÷120 min
0
Pr2
0÷23
-
rtc
0 ÷ 59
-
rtc
Sun ÷ SAt
-
rtc
Sun÷ SAt – nu
nu
Pr2
Sun÷ SAt – nu
nu
Pr2
0 ÷ 23h 50 min. - nu
6.0
rtc
0 ÷ 23h 50 min. - nu
13.0
rtc
0 ÷ 23h 50 min. - nu
21.0
rtc
0 ÷ 23h 50 min. - nu
nu
rtc
0 ÷ 23h 50 min. - nu
nu
rtc
0 ÷ 23h 50 min. - nu
nu
rtc
0 ÷ 23h 50 min. - nu
6.0
Pr2
13.0
0 ÷ 23h 50 min. - nu
Pr2
0 ÷ 23h 50 min. - nu
21.0
Pr2
0 ÷ 23h 50 min. - nu
nu
Pr2
0 ÷ 23h 50 min. - nu
nu
Pr2
0 ÷ 23h 50 min. - nu
nu
Pr2
0÷247
1
Pr2
nu, oFF; ES
oFF
Pr2
--
9.1
Pr2
--
--
Pr2
XR30CX
3/3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents