technical bulletin
Wiring Types
Retail Solutions specifies Belden #8641 shielded twisted pair cables for use as RS485 Bus wir-
ing (or Belden #82761 and Belden #88761 for plenum installations).
If the recommended cable is not available in your area, be sure the wiring meets or exceeds
the following specs:
Shielded?
Conductor Type
Gauge
Capacitance between
signal wires
Capacitance between
signal and shield
Maximum Length
Nominal Impedance
Table 3 - Cable Specs
Document Part # 026-4909 Rev 1 20-OCT-2011
©2011 Emerson Climate Technologies, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
Installation Instructions: XJ Scroll Condenser to E2
Yes
Twisted Pair
18 - 24 AWG
31 pF/ft or less
(9.45 m) or less
59 pF/ft or less
(17.98 m) or less
4000 ft/18 to 22 AWG
(1219.2 m)
2500 ft/24 AWG
(762 m)
12050