Condenser Fan(S); Liquid Receiver - Emerson Copeland EazyCool OM-15-PFJ Application Manuallines

Outdoor condensing units
Table of Contents

Advertisement

2.6.3

Condenser Fan(s)

The condensers of the Copeland EazyCool™ units are equipped with single-phase fans.
The "Q" versions are equipped with low speed (910 rpm) 6 pole single-phase fan motors.
Condensing Units
Medium Temp Low Temp
Standard
OM-15
OM-21
OL-09
OM-26
OL-11
OM-30
OL-13
OM-38
OL-15
OM-45
OL-18
Low Sound
OMQ-15
OMQ-21
OLQ-09
OMQ-26
OLQ-11
OMQ-30(D)
OLQ-13
OMQ-38
OLQ-15
OMQ-45(D)
OLQ-18
OMQ-56
OLQ-24V
OMQ-75
OLQ-33V
OMQ-92
OLQ-40V
OMQ-110
OLQ-48V
OMTQ-60(D)
OLTQ-26V
OMTQ-76
OLTQ-36V
OMTQ-90(D)
Table 3: Condenser fan: technical data
2.6.4

Liquid receiver

Copeland EazyCool™ condensing units are equipped with a liquid receiver with:
Rotalock service valve on top of the receiver for liquid outlet line.
3/8''–14 NPTF connection for relief valve. Maximum allowable working pressure -
MAWP 33 bar
Fitting a pressure relief device according to standard EN378-2 is the responsibility of the
installer.
Model Type
OM-15 & OL-09
OMQ-15 & OLQ-09
OM-21 to OM-45 & OL-11 to OL-18
OMQ-21 to OMQ-45(D) & OLQ-11 to OLQ-18
OMQ-56 to OMQ-110 & OLQ-24V to OLQ-48V
OMTQ-60(D) to OMTQ-90(D) & OLTQ-26V to OLTQ-36V
Table 4: Receiver volume
It is recommended to charge the system with refrigerant via the Rotalock service valves.
8
Run
N° of
Fan
Capacitor
fans
model
Capacity
1
121
4µF-400
1
271
6.3µF-400
1
65
3.15µF-400V
1
145
6.3µF-400V
2
145
6.3µF-400V
2
301
8µF-400V
2
145
6.3µF-400V
2
301
8µF-400V
Part No: 3125713
Power
Diameter Voltage
input
mm
V/ph/Hz
(W)
350
130
220-240
1~ 50
420
235
350
70
420
145
220-240
1~ 50
420
145
500
275
420
145
500
275
Rotalock service valve
Receiver
Volume
(l)
3.7
7.5
14
Relief valve connection
Current
Winding
input
resistance
(A)
Ohm (Ω)
0.66
68
1.38
19.1
0.38
143
0.81
45.9
0.81
45.9
1.56
24.7
0.81
45.9
1.56
24.7
C6.1.2/0105-0705/E

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents