Emerson XJAL-020Z-CFV-012 Manual page 55

Outdoor refrigeration unit
Table of Contents

Advertisement

technical bulletin
3. In the Connected I/O screen, under the ECT tab, Enter the number of XJ Scroll devices in the
XJ Scroll Unit number field.
4. Press
5. Locate the XJ Scroll units you added to the network list (press
list). The default name for an XJ Scroll begins with a two-letter designator of the model type
(XJ for XJ Scroll).
6. By default, each XJ Scroll's board number in the network list is indicated by a - (dash). To set
the address and begin communication, press  to Commission. (If you have more than one
Document Part # 026-4909 Rev 1 20-OCT-2011
©2011 Emerson Climate Technologies, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
Installation Instructions: XJ Scroll Condenser to E2
Figure 6 - Connected I/O Screen
to return to the Network Setup menu, then select
Figure 7 - Network Summary Screen
- Network Summary.
and
to scroll through the
Page 10 of 13