Installation; Qualified Oils & Refrigerant - Emerson KHZ506 User Manual

Table of Contents

Advertisement

Installation

The condensing unit should be located in such a place to prevent any dirt, plastic bag, leaves or papers from
covering the condenser and its fins. The unit must be installed without restricting the airflow. A clogged condenser
will increase the condensing temperature, thus reduce the cooling capacity, and lead to a high-pressure switch
tripping. Clean the condenser fins on a regular basis.
Before Installation
• Check all the LOTO tags, Working Space, operative should have correct tools etc.
• Ensure the units received are the correct models for the intended application.
• Ensure the refrigerant, voltage and gauges are all suitable for the proposed application & unit.
• Check there is no damage to the units.
• Check that the proposed equipment locations are suitable and provide adequate support for the weight
of the units.
During Installation and Subsequent Maintenance
• Installation and maintenance are to be performed only by qualified personnel who are familiar with
local codes and regulations and experienced with this type of equipment.
• As lifting equipment is required, ensure that it is suitable for purpose, certified and that the operators
are qualified to use it
• Safe working methods are identified, and operator have suitable PPE's.
• Ensure the working area has adequate ventilation during brazing procedures.
• Disconnect and shut off power before installation or service of the equipment
• Refrigerant release into the atmosphere is illegal. Proper evacuation, recovery, handling and leak
testing procedures must always be observed.
• Units must be earthed, and no maintenance work should be attempted prior to disconnecting the
electrical supply
• The electrical box/terminal covers, and fan guards must always remain fitted.
Note: All Compressors are delivered with sufficient oil for normal operation. The optimum oil level or oil
return should be checked by operating the compressor until the system is stable. It is not recommended
to top up Oil unnecessary. If required additional charge of oil for top-up or oil change during
maintenance or in case of leakage. kindly use our qualified oil as per below table recommended for
these Condensing units. Oil Level should not exceed 1/3
Oil & Refrigerant:
Qualified Refrigerant
Copeland® Brand
Products Standard Oils
Servicing Oils
of the Compressor sight glass.
rd
R404A
Emkarate RL 32 3MAF
Emkarate RL 32 3MAF
Mobil EAL Arctic 22 CC
10