Alarms/Warnings

Tab. 1 list all Alarms and Warnings, as well as explaining their effect on Dryer oper-
ation.
Whenever an alarm occurs, the current readings of temperatures and pressure are
registered in the status report (see para. 6.4).
Tab. 1 --- Alarms/Warnings
Alarm
Alarm/Warning
code
description
HP
High discharge pressure alarm
Ld
Low Dew Point alarm
IE
Inverter error
EP
Permanent memory error
FP
Fan thermal protection alarm
LP
Low suction pressure alarm
Hd
High Dew Point warning
AS1
Dew Point sensor fault
AS2
Evaporation temperature sensor fault
AS3
Suction temperature sensor fault
AS4
Ambient temperature sensor fault
AS5
Air inlet temperature sensor fault
AS6
Suction sensor pressure fault
HI
High air inlet temperature warning
HA
High ambient temperature warning
LA
Low ambient temperature warning
UA
User alarm
dA
Condensate drain alarm
PS
Programmed maintenance due --- Warning
Intervention
Action
delay
Dryer off
Immediate
Dryer off
Immediate
Dryer off
Immediate
Dryer off
Immediate
Dryer off
Immediate
Dryer off
Immediate
Programmable
Signal only
1÷60 min
Dryer off
Immediate
Dryer off
Immediate
Signal only
Immediate
Signal only
Immediate
Signal only
Immediate
Dryer off
Immediate
Signal only
Immediate
Signal only
Immediate
Signal only
Immediate
Programmable
See par. 6.3
0÷600 sec
Signal only
Immediate
Signal only
Immediate
6.3

User alarms

The Dryer is equipped with a user alarm input (terminals 51 and 66 of Dryer's ter-
minal board), useful to detect and signal a specific alarm condition, depending on
the user's needs. The user alarm is completely programmable in effect on Dryer's
operation, intervention delay, and reset mode.
S Parameter B12 selects the effect of user alarm intervention on Dryer's operation;
if its value is "run", the Dryer continues to work, and the alarm condition is only
signalled activating the alarm relay; if its value is "StoP", the Dryer stops.
S Parameter B13 allows a delay for the alarm intervention to be programmed (in the
range 0 --- 600 secs.).
S Parameter B14 selects the reset mode of user alarm, and has meaning only if the
effect is "StoP"; if its value is "Auto", the Dryer automatically restarts when the
alarm cause has been resolved; if its value is "MANUAL ", the alarm must be man-
ually reset (either through the button "alarm reset" or the input "remote reset",
terminals 51 and 64) for the Dryer to restart.