Parameters List; Resetting Alarms/Warnings - Sullair SRV-250 User Manual

Refrigeration dryer 60hz
Table of Contents

Advertisement

Available languages

Available languages

5.3

Parameters list

Type
No.
Description
A
1
Dryer working hours
A
2
Compressor working hours
A
3
ON time of drain valve (0=disabled)
A
4
OFF time of drain valve
A
5
Manually force ON drain valve
A
6
Metric/Imperial data reading
b
1
Maintenance due warning interval
b
2
Dryer working time reset
b
3
Compressor working time reset
b
4
Automatic restart after power interrupt
b
5
Automatic restart delay
Remote OFF (by contact or supervisor)
b
6
enable
b
7
Net identification number of dryer
b
8
Communication speed with supervisor
b
9
Communication protocol
b
10
Air inlet temperature sensor installed
b
11
Ambient temperature sensor installed
b
12
Effect of user alarm intervention
b
13
Signalling delay of user alarm
b
14
User alarm reset mode
b
15
High dew point warning temperature
b
16
High dew point warning delay
b
17
High air inlet temperature warning
b
18
High ambient temperature warning
b
19
Low ambient temperature warning
Alarm sound activation time
b
20
(0=continuously)
b
21
Version and revision number of software
b
22
Emission date of software
b
23
New password for "b" type parameters
Code: 02250144- - 517 SRV- - 250 --- SRV- - 2400
Range
Units
Default
0 ---999999
hours
0
0 ---999999
hours
0
0 ---100
secs
4
1 ---999
secs
170
no, YES
--- --- ---
no
˚C---bAr ˚F---PSI
--- --- ---
˚F---PSI
0 ---999999
hours
20000
no, YES
--- --- ---
no
no, YES
--- --- ---
no
no, YES
--- --- ---
YES
0 ---300
secs
0
no, YES, LOC
--- --- ---
no
1 ---200
--- --- ---
1
1200 ---19200
bits/sec
1200
ModbuS, CUStOM
--- --- ---
ModbuS
no, YES
--- --- ---
YES
no, YES
--- --- ---
YES
run, StOP
--- --- ---
run
0 ---600
secs
0
MANUAL, Auto
--- --- ---
Auto
˚C
10.0
0.0 ---30.0 ---32.0 ---86.0
˚F
50.0
1 ---60
mins
15
10 ---99
˚C
65.0
50 ---210
˚F
149.0
0 ---70
˚C
55
32 ---158
˚F
131
- - 30 ---30
˚C
2
- - 22 ---86
˚F
35.6
0 ---900
secs
0
--- --- ---
--- --- ---
--- --- ---
--- --- ---
--- --- ---
--- --- ---
1 ---32000
--- --- ---
0
6 Alarms
The Dryer features numerous Alarms and Warnings to ensure correct operation.
Warnings do not effect Dryer operation, whilst Alarms partially or totally block
Dryer operation.
NB: A voltage free General Alarm contact is provided, to allow remote Alarm signal-
ing (refer to Dryer's electrical diagram).
6.1

Resetting Alarms/Warnings

The following scheme outlines the procedure to be applied to reset an Alarm or
Warning.
S alarm siren sounds
S alarm LED turns on
S unit reacts as in Tab. 1
S "OFF" is displayed if the dryer stops.
ALARM/WARNING
intervention
alarm
press
reset
alarm siren is muted
alarm
press
reset
Alarm/Warning type is
displayed
alarm
press
reset
S alarm LED switches off
S display returns to normal
S unit returns to normal operation
English
9

Hide quick links: