BATCH interface blocks
2.2 IEOP
Rules for setting the status bits
● Static states are of highest importance in BATCH. The transition states are optional. The
● Only one static state and one transition state may be active simultaneously.
allowed:
HELD on its own
allowed:
ABORTING on its own
allowed:
HELD and ABORTING (useful in order to be able to detect the original state)
not allowed:
HELD and ABORTED
not allowed:
HOLDING and ABORTING
Note
Exception: The READY state may be set additive at another static state if the IREADY input
is used.
● A group error (bit 31) may be set in addition to any other state.
● The corresponding USTAT_L bit does not have to be set for entries in the "set if" column.
Batch messages
The block uses the associated values as follows:
Associated value 1 = batch name
Associated value 2 = step number
Associated value 3 = batch ID
Block parameters
QUSTAT_L bit 1
QUSTAT_L bit 2
QUSTAT_L bit 3
QUSTAT_L bit 4
QUSTAT_L bit 5
QUSTAT_L bit 6
QUSTAT_L bit 17
QUSTAT_L bit 18
QUSTAT_L bit 18
QUSTAT_L bit 19
QUSTAT_L bit 31
26
RUNNING state may be activated directly after the IDLE state, for example.
Example:
Value
Event
1
Operation in active state
1
Operation completed
1
Operation in hold state
1
Operation aborted
1
Operation ready to complete
1
Operation stopped
0
Operation in manual mode
0
Operation not enabled for BATCH
1
Operation enabled for BATCH
1
Operation runtime exceeded
1
Operation error
UBA_NAME
USTEP_N0
UBA_ID
Message class
Status message - AS
Status message - AS
Status message - AS
Status message - AS
Status message - AS
Status message - AS
Status message - AS
Status message - AS
Status message - AS
Status message - AS
AS process control system message
SIMATIC BATCH Interface Blocks V7.1
Function Manual, 03/2009, A5E02171101-01