Allocation of the status words USTAT_L and QUSTAT_L
Bit
Meaning
0
IDLE
1
RUNNING
2
COMPLETED
3
HELD
4
ABORTED
5
READY
6
STOPPED
7
Free
8
Free
9
STARTING
10
RESUMING
11
COMPLETING
12
HOLDING
13
ABORTING
14
STOPPING
15
Free
16
Reserved
17
QCMOD
18
BA_EN
19
STEP_RT
20
Reserved
21
REFRESH
22
LOCK
23
CONTINUOUS
24
OCCUPIED
25
PROC_ERR
26
Reserved
27
Reserved
28
Reserved
29
Reserved
30
Reserved
31
ERROR
SIMATIC BATCH Interface Blocks V7.1
Function Manual, 03/2009, A5E02171101-01
Remark
the static state is "inactive"
the static state is "active"
the static state is "completed"
the static state is "held"
the static state is "aborted"
the static state is "read to complete"
the static state is "stopped"
-
-
Transient state "starting"
Transient state "resuming"
Transient state "completing"
Transient state "holding"
Transient state "aborting"
Transient state "stopping"
-
(for SFC: Manual/Automatic mode requested)
Identifier: Manual/Automatic
(1 = automatic)
BATCH enable ID
(1 = enabled)
Identifier: Runtime exceeded
(for SFC: operator request transition)
Trigger for reading setpoints / actual values
Identifier: Start lock (1 = locked)
Identifier: Continuous mode
Identifier: BATCH allocation
(1 = occupied)
(for SFC: Process error)
(for SFC: Execution error)
(for SFC: Step runtime error)
(for SFC: Configuration error)
(for SFC: Operator input error)
(for SFC: External error)
Group error
BATCH interface blocks
2.2 IEOP
Set if
IREADY = 1
BA_EN = 1
Q_STEP_T > STEP_T
IREFRESH = 1
ILOCK = 1
ICONT = 1
OCCUPIED = 1